Investigation on the optimal cooling tower input capacity of a cooling tower assisted ground source heat pump system

被引:29
作者
Gong, Xuemei [1 ,3 ]
Xia, Lei [2 ]
Ma, Zhenjun [2 ]
Chen, Guangming [3 ]
Wei, Lili [1 ]
机构
[1] Ningbo Univ Technol, Bldg Energy Conservat Res Inst, Ningbo 315211, Zhejiang, Peoples R China
[2] Univ Wollongong, Sustainable Bldg Res Ctr, Wollongong, NSW 2522, Australia
[3] Zhejiang Univ, Inst Refrigerat & Cryogen, State Key Lab Clean Energy Utilizat, Hangzhou 310058, Zhejiang, Peoples R China
关键词
Hybrid ground source heat pump; Experiment; Simulation; Cooling tower; Input capacity ratio; Control strategy; THERMAL PERFORMANCE; OPTIMAL-DESIGN; OPERATION; EXCHANGERS; OPTIMIZATION; PARALLEL;
D O I
10.1016/j.enbuild.2018.06.024
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Coupling auxiliary cooling devices with ground source heat pump (GSHP) systems in cooling dominated areas can effectively solve the ground thermal imbalance problem. However, the input capacity of the auxiliary heat rejecter directly affects the performance of such hybrid ground source heat pump (HGSHP) systems. This paper presents an investigation on the optimal cooling tower input capacity of a cooling tower assisted GSHP system through both experiments and simulations. The experiments were carried out based on a HGSHP system implemented in an office building and the experimental results were used to validate a numerical model. A simulation system of the cooling tower assisted GSHP system was then developed using TRNSYS and validated against the experimental data collected. The impacts of the cooling tower input capacity on the soil temperature and the system performance were simulated. The results showed that the soil heat accumulation could be effectively alleviated when the cooling tower input capacity ratio (CTICR) was greater than 50%. The optimal cooling tower input capacity was highly dependent on the operation scenario used. The optimal CTICR under two operation scenarios considered was around 54%, while that under the other operation scenarios was around 63%. The control strategy based on the fixed temperature difference between the cooling water leaving the heat pump and the ambient air dry-bulb temperature was found to be the optimal control strategy for the system studied. (C) 2018 Elsevier B.V. All rights reserved.
引用
收藏
页码:239 / 253
页数:15
相关论文
共 35 条
[1]  
[Anonymous], 2009, GB503662009 MIN HOUS
[2]  
[Anonymous], 1992, SYST EQ
[3]  
[Anonymous], 2010, TECHN GUID BUILD APP
[4]  
[Anonymous], 2014, INT REFR AIR COND C
[5]  
ASHRAE, 1995, Commercial/institutional ground-source heat pump engineering manual
[6]  
Chiasson A.D., 2003, ASHRAE T, V109, P487
[7]   Optimization of design and operation parameters for hybrid ground-source heat pump assisted with cooling tower [J].
Cui, Wenzhi ;
Zhou, Shiyu ;
Liu, Xiangyang .
ENERGY AND BUILDINGS, 2015, 99 :253-262
[8]   Thermal performance and operation strategy optimization for a practical hybrid ground-source heat-pump system [J].
Fan, Rui ;
Gao, Yan ;
Hua, Li ;
Deng, Xiaoxi ;
Shi, Jie .
ENERGY AND BUILDINGS, 2014, 78 :238-247
[9]   Effective design and operation of hybrid ground-source heat pumps: Three case studies [J].
Hackel, Scott ;
Pertzborn, Amanda .
ENERGY AND BUILDINGS, 2011, 43 (12) :3497-3504
[10]  
Hellstrom G., 1991, Ground heat storage. Thermal analysis of Duct Storage Systems