Experimental study on double pipe PCM floor heating system under different operation strategies

被引:76
作者
Lu, Shilei [1 ]
Xu, Bowen [1 ]
Tang, Xiaolei [1 ]
机构
[1] Tianjin Univ, Sch Environm Sci & Engn, Tianjin 300072, Peoples R China
基金
国家重点研发计划;
关键词
Phase change material; Double-pipe; Floor heating system; Operation strategy; PHASE-CHANGE MATERIALS; THERMAL-ENERGY STORAGE; SHAPE-STABILIZED PCM; OF-THE-ART; BUILDING WALLS; PERFORMANCE; LATENT; ENHANCEMENT; VENTILATION; SIMULATION;
D O I
10.1016/j.renene.2019.06.086
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Phase change material (PCM) can be integrated into floor heating system to store excess heat, releasing it when needed, thus effectively reducing the mismatch between energy supply and demand. In this study, a double pipe PCM floor heating system with three independent heating modules was proposed for clean energy heating in rural China. A 26-day experimental study was conducted to study the operation effect of the system under four different strategies. Strategy 1: partial power operation strategy; Strategy 2: daytime energy storage strategy; Strategy 3: nocturnal energy storage strategy; and Strategy 4: phased energy storage strategy. In the early stage of heating, the average temperature of experiment room was 18.9 degrees C and the daily temperature fluctuation was controlled within 2.1 degrees C, which showed an effective guarantee of indoor comfort under Strategy 1. In the late stage of heating, the differences in indoor temperature fluctuations could be caused by changes in outdoor climate and operation strategies. And operating strategy had less impact on indoor temperature distribution. Moreover, the experiment results revealed that the system could provide a comfortable indoor thermal environment while adjusting operational strategies. And the 3 C average daily temperature fluctuation confirmed the feasibility of creating a comfortable environment with gentle temperature fluctuations via the PCM floor intermittent heating. (C) 2019 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1280 / 1291
页数:12
相关论文
共 44 条
[1]   A newly composed paraffin encapsulated prototype roof structure for efficient thermal management in hot climate [J].
Akeiber, Hussein J. ;
Wahid, Mazlan A. ;
Hussen, Hasanen M. ;
Mohammad, Abdulrahman Th. .
ENERGY, 2016, 104 :99-106
[2]   Experimental study on the cooling capacity of a radiant cooled ceiling system [J].
Andres-Chicote, Manuel ;
Tejero-Gonzalez, Ana ;
Velasco-Gomez, Eloy ;
Javier Rey-Martinez, Francisco .
ENERGY AND BUILDINGS, 2012, 54 :207-214
[3]   FLOOR RADIANT SYSTEM WITH HEAT-STORAGE BY A SOLID SOLID-PHASE TRANSITION MATERIAL [J].
BARRIO, M ;
FONT, J ;
LOPEZ, DO ;
MUNTASELL, J ;
TAMARIT, JL .
SOLAR ENERGY MATERIALS AND SOLAR CELLS, 1992, 27 (02) :127-133
[4]  
Barzin R., 2016, APPL ENERG, V401, P347
[5]   Application of weather forecast in conjunction with price-based method for PCM solar passive buildings - An experimental study [J].
Barzin, Reza ;
Chen, John J. J. ;
Young, Brent R. ;
Farid, Mohammed M. .
APPLIED ENERGY, 2016, 163 :9-18
[6]   Application of PCM energy storage in combination with night ventilation for space cooling [J].
Barzin, Reza ;
Chen, John J. J. ;
Young, Brent R. ;
Farid, Mohammed M. .
APPLIED ENERGY, 2015, 158 :412-421
[7]   Energetic and financial evaluation of solar assisted heat pump space heating systems [J].
Bellos, Evangelos ;
Tzivanidis, Christos ;
Moschos, Konstantinos ;
Antonopoulos, Kimon A. .
ENERGY CONVERSION AND MANAGEMENT, 2016, 120 :306-319
[8]   Optimisation analysis of PCM-enhanced opaque building envelope components for the energy retrofitting of office buildings in Mediterranean climates [J].
Cascone, Ylenia ;
Capozzoli, Alfonso ;
Perino, Marco .
APPLIED ENERGY, 2018, 211 :929-953
[9]   Effect of thermal conductivities of shape stabilized PCM on under-floor heating system [J].
Cheng, Wenlong ;
Xie, Biao ;
Zhang, Rongming ;
Xu, Zhiming ;
Xia, Yuting .
APPLIED ENERGY, 2015, 144 :10-18
[10]   Dynamics of external wall structures with a PCM (phase change materials) in high latitude countries [J].
Chwieduk, Dorota A. .
ENERGY, 2013, 59 :301-313