Experimental research of the guiding channels effect on the thermal performance of wet cooling towers subjected to crosswinds - Air guiding effect on cooling tower

被引:42
作者
Wang, Kai [1 ]
Sun, Feng-zhong [1 ]
Zhao, Yuan-bin [1 ]
Gao, Ming [1 ]
Ruan, Lei [2 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
[2] So Suburbs Thermal Elect Power Plant, Jinan 250000, Peoples R China
关键词
Cooling tower; Air guiding channels; Crosswinds; Thermal performance; Model test; INTAKE FLOW-RATE; ARTIFICIAL NEURAL-NETWORK; NUMERICAL-SIMULATION; WIND CONDITIONS; PREDICTION; EFFICIENCY;
D O I
10.1016/j.applthermaleng.2009.10.015
中图分类号
O414.1 [热力学];
学科分类号
摘要
The thermal performance of a natural-draft wet cooling tower model with inlet airflow guiding channels under crosswinds conditions was monitored and experimented. Three patterns of the air guiding channels with different setting angles (including 60 degrees, 70 degrees and 80 degrees) were tested under various crosswinds velocities. The results show that the air flow rate and the cooling efficiency increase remarkably after the inlet air is directed. On the basis of testing data, some thermal performance parameters including the Lewis factor, the heat and mass transfer coefficient were also calculated and analysed. The results indicate that the Lewis factor ranges from 0.95 to 1.15, which is in accordance with the data of other literatures. Besides, it is found that the optimum setting angle for the air guiding channels is 70 degrees, and it does not change with the channel quantity which ranges from 18 to 88. However, it should be noticed that although the guiding channels with 70 degrees setting angle lead to better cooling performance, they may cause more circulating water consumption. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:533 / 538
页数:6
相关论文
共 18 条