Fault Characteristics Analysis and Line Protection Design Within a Large-Scale Photovoltaic Power Plant

被引:74
作者
Jia, Ke [1 ]
Gu, Chenjie [2 ]
Xuan, Zhenwen [1 ]
Li, Lun [1 ]
Lin, Yaoqi [1 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternat Elect Power Syst Renewable, Beijing 102206, Peoples R China
[2] State Grid Suzhou Power Supply Co, Suzhou 215000, Peoples R China
关键词
Centralized photovoltaic power plant; distance relay; fault current analysis; overcurrent relay (OCR); relay scheme; DISTRIBUTED GENERATION; DISTRIBUTION-SYSTEMS; CONTROL SCHEME; GRID FAULTS; NETWORKS; CONVERTERS; INVERTERS;
D O I
10.1109/TSG.2017.2648879
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Centralized photovoltaic (PV) systems have different fault characteristics from distributed PV systems due to the different system structures and controls. This makes the fault analysis and protection methods used in distribution networks with distributed PV not suitable for a centralized PV power plant. Therefore, a consolidated expression for the fault current within a PV power plant under different controls was calculated considering the fault response of the PV array. Then, supported by the fault current analysis and the field-testing data, the over current relay (OCR) performance was evaluated in the collection system of an 850 MW PV power plant. It reveals that the OCRs at PV side on overhead lines may malfunction. In this case, a new relay scheme was proposed using directional distance elements. In PSCAD/EMTDC, a detailed PV system model was built and verified using the field-testing data. Simulation results indicate that the proposed relay scheme could effectively solve the problems under variant fault scenarios and PV plant output levels.
引用
收藏
页码:4099 / 4108
页数:10
相关论文
共 30 条
[1]   Optimal Distributed Generation Allocation and Sizing in Distribution Systems via Artificial Bee Colony Algorithm [J].
Abu-Mouti, Fahad S. ;
El-Hawary, M. E. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) :2090-2101
[2]  
[Anonymous], GTM RES GLOBAL SOLAR
[3]   Fault analysis on distribution feeders with distributed generators [J].
Baran, ME ;
El-Markaby, I .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (04) :1757-1764
[4]   Grid-Fault Control Scheme for Three-Phase Photovoltaic Inverters With Adjustable Power Quality Characteristics [J].
Castilla, Miguel ;
Miret, Jaume ;
Luis Sosa, Jorge ;
Matas, Jose ;
Garcia de Vicuna, Luis .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2010, 25 (12) :2930-2940
[5]  
Dewadasa M, 2011, IEEE IND ELEC, P924
[6]   Current phase comparison pilot scheme for distributed generation networks protection [J].
El Halabi, N. ;
Garcia-Gracia, M. ;
Borroy, J. ;
Villa, J. L. .
APPLIED ENERGY, 2011, 88 (12) :4563-4569
[7]   Tunning of Phase Locked Loops for Power Converters under Distorted Utility Conditions [J].
Freijedo, Francisco D. ;
Doval-Gandoy, Jesus ;
Lopez, Oscar ;
Acha, Enrique .
APEC: 2009 IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION, VOLS 1- 4, 2009, :1733-+
[8]  
Guo X, 2014, PROC IEEE INT SYMP, P2354, DOI 10.1109/ISIE.2014.6864987
[9]   Flexible Control Strategy for Grid-Connected Inverter Under Unbalanced Grid Faults Without PLL [J].
Guo, Xiaoqiang ;
Liu, Wenzhao ;
Zhang, Xue ;
Sun, Xiaofeng ;
Lu, Zhigang ;
Guerrero, Josep M. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (04) :1773-1778
[10]   Multiple-Complex Coefficient-Filter-Based Phase-Locked Loop and Synchronization Technique for Three-Phase Grid-Interfaced Converters in Distributed Utility Networks [J].
Guo, Xiaoqiang ;
Wu, Weiyang ;
Chen, Zhe .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (04) :1194-1204