Decreasing the commutation failure frequency in HVDC transmission systems

被引:63
作者
Hansen, A [1 ]
Havemann, K [1 ]
机构
[1] Tech Univ Denmark, Dept Elect Power Engn, DK-2800 Lyngby, Denmark
关键词
commutation failures; digital control; HVDC; transmission;
D O I
10.1109/61.871369
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper we show how a fairly targe proportion of those commutation failures that are due to single-phased short circuits to earth can he avoided. In a control circuit based on a digital signal processor (DSP) it is possible, with instantaneous results, to switch from a normal control strategy with equidistant firing pulses to a strategy that takes into consideration the potentially dangerous voltage changes on the supply lines, IF the supply voltages are monitored continuously, it is possible to calculate the necessity of advancing the bring pulses to avoid commutation failures, In the paper such a calculation technique is described. The monitoring times may be approximately 50 mu sec apart corresponding to a distance of 0.016 radians or about 1 degrees.
引用
收藏
页码:1022 / 1026
页数:5
相关论文
共 3 条
[1]   A MICROPROCESSOR-BASED CONTROLLER FOR A 3-PHASE CONTROLLED RECTIFIER BRIDGE [J].
DEWAN, SB ;
DUNFORD, WG .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1983, 19 (01) :113-119
[2]  
Sood V. K., 1995, International Conference on Power Systems Transients. IPST '95 Proceedings, P517
[3]   Commutation failures in HVDC transmission systems [J].
Thio, CV ;
Davies, JB ;
Kent, KL .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (02) :946-957