TEWI Assessment of Conventional and Solar Powered Cooling Systems

被引:14
作者
Islam, Md Amirul [1 ,2 ,3 ]
Saha, Bidyut Baran [1 ,2 ]
机构
[1] Kyushu Univ, Program Leading Grad Sch, Green Asia Educ Ctr, IGSES, Kasuga Koen 6-1, Kasuga, Fukuoka 8168580, Japan
[2] Kyushu Univ, Int Inst Carbon Neutral Energy Res WPI ICNER, Nishi Ku, 744 Motooka, Fukuoka 8190395, Japan
[3] Bangabandhu Sheikh Mujibur Rahman Sci & Technol U, Dept Elect & Telecommun Engn, Gopalganj 8100, Bangladesh
来源
SOLAR ENERGY: SYSTEMS, CHALLENGES, AND OPPORTUNITIES | 2020年
关键词
Adsorption cooling; GWP; HFC; Solar thermal energy; TEWI; Vapor compression refrigeration; COMPRESSION REFRIGERATION SYSTEM; ACTIVATED CARBON; ADSORPTION CHILLER; SILICA-GEL; ENVIRONMENTAL IMPACTS; HEAT; PERFORMANCE; WATER; WORKING; ENERGY;
D O I
10.1007/978-981-15-0675-8_9
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Conventional cooling and refrigeration systems already evolved to efficient design, have higher COP and compact size. However, the compressor section of such system consumes a tremendous amount of electricity and contribute indirectly to global warming. The working fluids of these systems are typically HFC or HFC blends which possess very high global warming potential. A significant percentage of working fluid is leaked from the high-pressure side of the system and directly contribute to global warming. The summation of indirect and direct warming impact, namely, total equivalent warming impact (TEWI) of the vapour compression cooling systems are significantly high. Adsorption cooling system (ACS) can resolve this critical issue. In ACS, the mechanical compressor of the traditional cooling system is replaced by a thermal compressor, namely, a pair of adsorption beds. Highly porous adsorbent material (silica gel, activated carbon, zeolite and so forth) is the key component of an adsorption bed. These materials have the capability to capture and hold certain types of fluid. This phenomenon is known as adsorption. Upon heating, the adsorbed fluid is liberated from the pores (desorption process) and gets thermally compressed. Solar thermal energy is the most prospective option for the desorption process to occur. Since there is no mechanical compressor, electricity consumption is deficient, which significantly minimizes the indirect warming impact. Moreover, natural or alternative refrigerants are used as the working fluid, which has zero/negligible GWP. Hence, the direct warming impact is also shallow. In this chapter, the working principle and governing equations of a solar energy driven adsorption cooling system will be elaborated. Besides, TEWI assessment procedure will be explained and compared for both vapour compression and adsorption cooling systems.
引用
收藏
页码:147 / 177
页数:31
相关论文
共 86 条
[1]   Natural and synthetic refrigerants, global warming: A review [J].
Abas, Naeem ;
Kalair, Ali Raza ;
Khan, Nasrullah ;
Haider, Aun ;
Saleem, Zahid ;
Saleem, Muhammad Shoaib .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 90 :557-569
[2]   A review on exergy analysis of vapor compression refrigeration system [J].
Ahamed, J. U. ;
Saidur, R. ;
Masjuki, H. H. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2011, 15 (03) :1593-1600
[3]   Optimal design study of cylindrical finned reactor for solar adsorption cooling machine working with activated carbon-ammonia pair [J].
Al Mers, A. ;
Azzabakh, A. ;
Mimet, A. ;
El Kalkha, H. .
APPLIED THERMAL ENGINEERING, 2006, 26 (16) :1866-1875
[4]   Performance evaluation of a solar adsorption chiller under different climatic conditions [J].
Alahmer, Ali ;
Wang, Xiaolin ;
Al-Rbaihat, Raed ;
Alam, K. C. Amanul ;
Saha, B. B. .
APPLIED ENERGY, 2016, 175 :293-304
[5]  
[Anonymous], Technical Specification for ADS-L transmissions using SRD-860 frequency band (ADS-L 4 SRD-860)
[6]  
[Anonymous], 2015, Combined Cooling, Heating and Power Decision-Making, Design and Optimization, DOI DOI 10.1016/C2013-0-18763-6
[7]  
[Anonymous], Hitachi Room Aircon Product Brochure
[8]  
[Anonymous], STANDARD SPECIFICATI
[9]  
[Anonymous], Mitsubishi Plastics launches a compact adsorption chiller with the highest cooling capacity per volume in the world
[10]  
[Anonymous], 2018, Key World Energy Statistics