Breakdown Characteristics of Transformer Oil in a Uniform Field under Oscillating Impulse Voltage

被引:9
作者
Li, Junhao [1 ]
Zhang, Liang [1 ]
Jin, Yuhui [1 ]
Yao, Xiu [2 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian, Peoples R China
[2] SUNY Buffalo, Dept Elect Engn, Buffalo, NY USA
关键词
Breakdown characteristics; transformer oil; oscillating impulse voltage; uniform filed; INSULATION CHARACTERISTICS; IMMERSED TRANSFORMERS; MINERAL-OIL; WAVE-FORMS; STREAMERS; STANDARD;
D O I
10.1109/TDEI.2017.005996
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The field impulse voltage test plays the most important role to ensure the safe of the power transformer. It is hard to carry out the standard impulse voltage test for the power equipment because the generator is very huge. The oscillating impulse voltage waveform has high efficiency and be recommended by IEC 60060-3 as the field test waveform. Transformer oil is the main insulation part of power transformer insulation system. The insulation characteristics of transformer oil under different type impulse waveform have great influence to the design, operation and test amplitude for the power transformer. This paper focuses on the breakdown characteristics of transformer oil in a uniform field under oscillating impulse voltage (OIV). Three type oscillating impulse voltage waveforms with oscillating frequency of 14, 117 and 373 kHz were adopted as the test waveforms. The standard lightning impulse (SLI) voltage was also adopted as the reference waveform. The experiment results show the breakdown waveforms have large oscillation under OIV but little oscillation under SLI for the influence of circuit inductor. The minimum breakdown voltage increase with the increase of oscillating frequency and the 117 kHz impulse waveform has the similar breakdown voltage with SLI waveform. The voltage-time distributions were obtained through lab test and the results shown that the OIV have the longer time lag than SLI for the influence of the oscillation of waveform. The experimental results were explained through streamer mechanism. The study provides the foundation for the field impulse test using oscillating impulse waveform.
引用
收藏
页码:984 / 990
页数:7
相关论文
共 23 条
[1]  
[Anonymous], 2005, IEC600603
[2]  
Bhuyan K., 2010, JOINT INT C POWER EL, P1
[3]   Electric stresses on transformer winding insulation under standard and non-standard impulse voltages [J].
Bhuyan, Kaveri ;
Chatterjee, Saibal .
ELECTRIC POWER SYSTEMS RESEARCH, 2015, 123 :40-47
[4]   PARTIAL DISCHARGES AND STREAMERS IN LIQUID DIELECTRICS - THE SIGNIFICANCE OF THE INCEPTION VOLTAGE [J].
FORSTER, EO .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (06) :941-946
[5]   Streamers in water and other dielectric liquids [J].
Kolb, J. F. ;
Joshi, R. P. ;
Xiao, S. ;
Schoenbach, K. H. .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2008, 41 (23)
[6]   Partial Discharge Characteristics over Differently Aged Oil/pressboard Interfaces [J].
Li, Junhao ;
Si, Wenrong ;
Yao, Xiu ;
Li, Yanming .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (06) :1640-1647
[7]   Study on Oscillating Switching Impulse Voltage Generation for Power Transformer Onsite Test [J].
Liang, Jianfeng ;
Zhang, Liang ;
Li, Junhao ;
Li, Yanming .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (05) :2223-2230
[8]  
Liu RS, 2005, I C DIELECT LIQUIDS, P75
[9]   A comparison of negative and positive streamers in mineral oil at large gaps [J].
Massala, G ;
Lesaint, O .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2001, 34 (10) :1525-1532
[10]   BREAKDOWN AND PREBREAKDOWN PHENOMENA IN LIQUIDS UNDER POSITIVE IMPULSE VOLTAGES [J].
MCCLUSKEY, FMJ ;
DENAT, A ;
LESAINT, O .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1994, 1 (03) :377-382