An experimental study of the air-side performance of fin-and-tube heat exchangers having plain, louver, and semi-dimple vortex generator configuration

被引:79
|
作者
Wang, Chi-Chuan [1 ]
Chen, Kuan-Yu [1 ]
Liaw, Jane-Sunn [2 ]
Tseng, Chih-Yung [2 ]
机构
[1] Natl Chiao Tung Univ, Dept Mech Engn, Hsinchu 300, Taiwan
[2] Ind Technol Res Inst, Green Energy & Environm Res Labs, Hsinchu 310, Taiwan
关键词
Fin-and-tube heat exchanger; Louver fin; Vortex generator; TRANSFER ENHANCEMENT; PLATE-FIN; RECENT PATENTS; FLOW; VORTICES; SURFACES; ROWS;
D O I
10.1016/j.ijheatmasstransfer.2014.09.030
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, a comparative study of the airside performance of fin-and-tube heat exchangers having plain, louver, and semi-dimple vortex generator (VG) are made. A total of eighteen samples are made and tested with the corresponding fin pitch (F-p) being 1.6 mm and 2.0 mm and the number of tube row (N) are 1, 2 and 4, respectively. Test results indicate that the heat transfer coefficient for N = 1 for louver fin geometry with a smaller fin pitch of 1.6 mm is higher than that of semi-dimple VG and plain fin geometry. For N = 1 with a larger fin pitch of 2.0 mm, the semi-dimple VG is marginally higher than that of louver fin geometry when the frontal velocity is lower than 2 m s(-1). However, the trend is reversed where the heat transfer coefficient for louver fin outperforms that of semi-dimple VG when the velocity is increased further. For the airside performance for N = 2 or N = 4, the heat transfer coefficients for louver fin geometry is about 2-15% higher than those of semi-dimple geometry. The difference is increased with the rising velocity and the results prevail for both fin pitches. However, the difference is smaller at a larger fin pitch due to the comparatively effectively swirled motion of the semi-dimple VG. The effect of the number of tube row on the heat transfer coefficients is negligible for louver fin geometry and is also rather small for semi-dimple VG. For the plain fin geometry, the effect of tube row is also small when N > 1. The heat transfer performance for N = 1 is different from N = 2 or N = 4 due to its inline configuration. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:281 / 287
页数:7
相关论文
共 48 条
  • [31] Experimental Study of the Air Side Performance of Fin-and-Tube Heat Exchanger with Different Fin Material in Dehumidifying Conditions
    Hu, Wan-Ling
    Ma, Ai-Jun
    Guan, Yong
    Cui, Zhi-Jie
    Zhang, Yi-Bo
    Wang, Jing
    ENERGIES, 2021, 14 (21)
  • [32] A numerical study on the air-side heat transfer of perforated finned-tube heat exchangers with large fin pitches
    Liu, Xiaoqin
    Yu, Jianlin
    Yan, Gang
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 100 : 199 - 207
  • [33] Effects of fin pitch and tube diameter on the air-side performance of tube bank fin heat exchanger with the fins punched plane and curved rectangular vortex generators
    Tian, Xing-Lu
    Jin, Hua
    Song, Ke-Wei
    Wang, Liang-Chen
    Liu, Song
    Wang, Liang-Bi
    EXPERIMENTAL HEAT TRANSFER, 2018, 31 (04) : 297 - 316
  • [34] Parametric study and multiple correlations on air-side heat transfer and friction characteristics of fin-and-tube heat exchangers with large number of large-diameter tube rows
    Xie, Gongnan
    Wang, Qiuwang
    Sunden, Bengt
    APPLIED THERMAL ENGINEERING, 2009, 29 (01) : 1 - 16
  • [35] Numerical Study of Fin-and-Tube Heat Exchanger in Low-Pressure Environment: Air-Side Heat Transfer and Frictional Performance, Entropy Generation Analysis, and Model Development
    Zhang, Lei
    Wang, Junwei
    Liu, Ran
    Li, Guohua
    Han, Xiao
    Zhang, Zhiqiang
    Zhao, Jiayi
    Dai, Baomin
    ENTROPY, 2022, 24 (07)
  • [36] AIR-SIDE HEAT TRANSFER ENHANCEMENT BY A NOVEL WINGLET-TYPE VORTEX GENERATOR ARRAY IN A ROUND-TUBE PLAIN-FIN HEAT EXCHANGER
    He, Jing
    Liu, Liping
    Jacobi, Anthony M.
    HT2009: PROCEEDINGS OF THE ASME SUMMER HEAT TRANSFER CONFERENCE 2009, VOL 1, 2009, : 575 - 582
  • [37] Experimental Study on the Heat Transfer Performance and Pressure Drop of Fin-and-Tube Heat Exchangers Having Non-symmetric Slit Fins
    Kim, Nae-Hyun
    TRANSACTIONS OF THE KOREAN SOCIETY OF MECHANICAL ENGINEERS B, 2019, 43 (09) : 661 - 669
  • [38] Numerical study of the air inlet angle influence on the air-side performance of plate-fin heat exchangers
    Liu, Zhiying
    Li, Hui
    Shi, Lin
    Zhang, Yangjun
    APPLIED THERMAL ENGINEERING, 2015, 89 : 356 - 364
  • [39] Experimental study of the effect of air inlet angle on the air-side performance for cross-flow finned oval-tube heat exchangers
    Du, X. P.
    Zeng, M.
    Dong, Z. Y.
    Wang, Q. W.
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2014, 52 : 146 - 155
  • [40] NUMERICAL INVESTIGATION ON AIR SIDE PERFORMANCE OF FIN-AND-TUBE HEAT EXCHANGERS WITH LARGE DIAMETER TUBES AND LARGE NUMBER OF TUBE ROWS
    Zhou, Feng
    Geb, David
    Catton, Ivan
    PROCEEDINGS OF THE ASME INTERNATIONAL MECHANICAL ENGINEERING CONGRESS AND EXPOSITION, 2011, VOL 1, 2012, : 805 - 813