An experimental study of the air-side performance of fin-and-tube heat exchangers having plain, louver, and semi-dimple vortex generator configuration

被引:79
|
作者
Wang, Chi-Chuan [1 ]
Chen, Kuan-Yu [1 ]
Liaw, Jane-Sunn [2 ]
Tseng, Chih-Yung [2 ]
机构
[1] Natl Chiao Tung Univ, Dept Mech Engn, Hsinchu 300, Taiwan
[2] Ind Technol Res Inst, Green Energy & Environm Res Labs, Hsinchu 310, Taiwan
关键词
Fin-and-tube heat exchanger; Louver fin; Vortex generator; TRANSFER ENHANCEMENT; PLATE-FIN; RECENT PATENTS; FLOW; VORTICES; SURFACES; ROWS;
D O I
10.1016/j.ijheatmasstransfer.2014.09.030
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, a comparative study of the airside performance of fin-and-tube heat exchangers having plain, louver, and semi-dimple vortex generator (VG) are made. A total of eighteen samples are made and tested with the corresponding fin pitch (F-p) being 1.6 mm and 2.0 mm and the number of tube row (N) are 1, 2 and 4, respectively. Test results indicate that the heat transfer coefficient for N = 1 for louver fin geometry with a smaller fin pitch of 1.6 mm is higher than that of semi-dimple VG and plain fin geometry. For N = 1 with a larger fin pitch of 2.0 mm, the semi-dimple VG is marginally higher than that of louver fin geometry when the frontal velocity is lower than 2 m s(-1). However, the trend is reversed where the heat transfer coefficient for louver fin outperforms that of semi-dimple VG when the velocity is increased further. For the airside performance for N = 2 or N = 4, the heat transfer coefficients for louver fin geometry is about 2-15% higher than those of semi-dimple geometry. The difference is increased with the rising velocity and the results prevail for both fin pitches. However, the difference is smaller at a larger fin pitch due to the comparatively effectively swirled motion of the semi-dimple VG. The effect of the number of tube row on the heat transfer coefficients is negligible for louver fin geometry and is also rather small for semi-dimple VG. For the plain fin geometry, the effect of tube row is also small when N > 1. The heat transfer performance for N = 1 is different from N = 2 or N = 4 due to its inline configuration. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:281 / 287
页数:7
相关论文
共 48 条
  • [1] Investigation of the semi-dimple vortex generator applicable to fin-and-tube heat exchangers
    Wang, Chi-Chuan
    Chen, Kuan-Yu
    Lin, Yur-Tsai
    APPLIED THERMAL ENGINEERING, 2015, 88 : 192 - 197
  • [2] Effects of curved vortex generators on the air-side performance of fin-and-tube heat exchangers
    Lu, Gaofeng
    Zhai, Xiaoqiang
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2019, 136 : 509 - 518
  • [3] An experimental study of the air-side performance of a novel louver spiral fin-and-tube heat exchanger
    Kiatpachai, Parinya
    Keawkamrop, Thawatchai
    Asirvatham, Lazarus Godson
    Mesgarpour, Mehrdad
    Dalkilic, Ahmet Selim
    Ahn, Ho Seon
    Mahian, Omid
    Wongwises, Somchai
    ALEXANDRIA ENGINEERING JOURNAL, 2022, 61 (12) : 9811 - 9818
  • [4] Experimental and numerical investigation on air-side performance of fin-and-tube heat exchangers with various fin patterns
    Tang, L. H.
    Zeng, M.
    Wang, Q. W.
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2009, 33 (05) : 818 - 827
  • [5] Optimal design of the semi-dimple vortex generator in the fin and tube heat exchanger
    Chimres, Nares
    Wang, Chi-Chuan
    Wongwises, Somchai
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 120 : 1173 - 1186
  • [6] An experimental investigation of the air-side performance of crimped spiral fin-and-tube heat exchangers with a small tube diameter
    Keawkamrop, Hawatchai
    Asirvatham, Lazarus Godson
    Dalkilic, Ahmet Selim
    Ahn, Ho Seon
    Mahian, Omid
    Wongwi, Somchai
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2021, 178
  • [7] Numerical investigation of the air-side performance of louver fin-and-tube radiators having rectangular, tapered and airfoil section configuration
    Zhang, Xiang
    Huang, Ying
    Song, Jiangnan
    Ma, Zongpeng
    Chen, Lunjun
    Li, Taike
    ENERGY REPORTS, 2022, 8 : 11799 - 11809
  • [8] Air-side performance of serrated welded spiral fin-and-tube heat exchangers
    Kiatpachai, Parinya
    Pikulkajorn, Santi
    Wongwises, Somchai
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 89 : 724 - 732
  • [9] Parametric study of the air-side performance of slit fin-and-tube heat exchangers in wet conditions
    Wang, CC
    Lee, WS
    Sheu, WJ
    Chang, YJ
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART C-JOURNAL OF MECHANICAL ENGINEERING SCIENCE, 2001, 215 (09) : 1111 - 1121
  • [10] Effect of fin pitches on the air-side performance of L-footed spiral fin-and-tube heat exchangers
    Pongsoi, Parinya
    Promoppatum, Patcharapit
    Pikulkajorn, Santi
    Wongwises, Somchai
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2013, 59 : 75 - 82