Insulation design of 25.8kV class gas insulated switchgear in Dry Air

被引:0
|
作者
Lee, Hakju [1 ]
Yeun, Jeuk [1 ]
Ahn, Heesub [1 ]
Choi, Jongung [2 ]
Kim, Yonggun [3 ]
机构
[1] LS ELECT Co Ltd, HV GIS R&D Team, Anyang, South Korea
[2] LS ELECT Co Ltd, HV R&D Ctr, Anyang, South Korea
[3] LS ELECT Co Ltd, R&D Campus, Anyang, South Korea
来源
2022 6TH INTERNATIONAL CONFERENCE ON ELECTRIC POWER EQUIPMENT - SWITCHING TECHNOLOGY (ICEPE-ST) | 2022年
关键词
Gas insulated switchgear; Switchgear design; Dry Air; Dielectric test; Breakdown;
D O I
10.1109/ICEPE-ST51904.2022.9757091
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Research on Eco-friendly gas used in gas insulated switchgear (GIS) has been studied in earnest since the Paris Climate Change Accord in 2015. Existing SF6 gas has excellent dielectric strength, but has a high global warming potential (GWP). On the other hand, dry air is easy to use in low voltage GIS because it has a lower global warming potential and low dielectric strength than SF6 gas. In this paper, the results of insulation test and electric field analysis of 25.8kV class gas insulated switchgear in Dry Air. The test was conducted with the test method of IEC 62271-1 "Dielectric tests". As a result of lightning impulse tests, insulation breakdown occurred in various shapes. Ansys Maxwell 3D electric field analysis was performed based on the test results.
引用
收藏
页码:253 / 256
页数:4
相关论文
共 50 条
  • [1] Optimal Insulation Design of 25.8kV Environment-friendly Insulated Switch Based on Taguchi Method
    Yu, Lyun
    Kim, Young-Moon
    Ahn, Kil-Young
    Kim, Young-Geun
    Jo, Hae-Yong
    Transactions of the Korean Institute of Electrical Engineers, 2022, 71 (07): : 1034 - 1039
  • [2] Insulation Technology in Dry Air and Vacuum for a 72-kV Low-Pressure Dry-Air Insulated Switchgear
    Yoshida, Tadahiro
    Koga, Hiromi
    Harada, Takakazu
    Miki, Shinichi
    Arioka, Masahiro
    Sato, Shinji
    Yoshida, Satoru
    Inoue, Naoaki
    Maruyama, Akihiko
    Takeuchi, Toshie
    ELECTRICAL ENGINEERING IN JAPAN, 2011, 175 (01) : 18 - 24
  • [3] Discussion on the electrical insulation design of the HVDC Gas Insulated Switchgear
    Wang, Feng
    Qiu, Yu-Chang
    Zhongguo Dianli/Electric Power, 2002, 35 (11):
  • [4] Comparison of the attenuation measurement methods for electromagnetic partial discharge signal in 25.8 kV gas insulated switchgear
    Goo, Sun-Geun
    Han, Ki-Sun
    Kwak, Joo-Sik
    Joo, Hyung-Jun
    Jeong, Moon-Gyu
    Transactions of the Korean Institute of Electrical Engineers, 2015, 64 (09): : 1281 - 1287
  • [5] Redesign Gas Insulated Switchgear to Semi Air Insulated Switchgear 500 kV side and 150 kV side in EHVS Kembangan
    Damiri, D. J.
    Prasetio, T. W.
    5TH ANNUAL APPLIED SCIENCE AND ENGINEERING CONFERENCE (AASEC 2020), 2021, 1098
  • [6] 800 KV GAS INSULATED SWITCHGEAR
    OISHI, M
    OZAKI, Y
    YANABU, S
    TOSHIBA REVIEW, 1986, (155): : 8 - 12
  • [7] Gas and Solid Insulation in HVDC Gas Insulated Switchgear
    Zhong, Jianying
    Zhang, Bo
    Guo, Yujing
    Wang, Zhijun
    Yao, Yongqi
    Zhang, Hao
    Liu, Yapei
    2017 IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2017,
  • [8] 800 KV GAS INSULATED SWITCHGEAR.
    Oishi, Motoyuki
    Ozaki, Yasuo
    Yanabu, Satoru
    Toshiba review International ed., 1986, (155): : 8 - 12
  • [10] Gas generation characteristics for solid insulation defects in the gas insulated switchgear
    Sha Y.
    Cai W.
    Li D.
    Li Z.
    Xu D.
    Long K.