Investigation on Lightning Impulse Breakdown and Dissolved Gas Characteristics of the Novel Three-element Mixed Insulation Oil

被引:0
|
作者
Chen Xin [1 ]
Hao Jian [1 ]
Yang Lijun [1 ]
Liu Xiong [2 ]
Liao Ruijin [1 ]
Feng Dawei [1 ]
Wang Qian [2 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400044, Peoples R China
[2] State Grid Chongqing Elect Power Co, Chongqing Elect Power Res Inst, Chongqing 401123, Peoples R China
来源
2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019) | 2019年
关键词
D O I
10.1109/icempe.2019.8727290
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As a kind of potential alternative of traditional mineral insulation oil, mixed oil gives rise to numerous researches on its physicochemical and insulation properties. On this background, a novel three- element mixed insulation oil was developed successfully by our team. Its key parameters meet the requirements of IEC 60296:2012. In order to promote the application of the novel three-element mixed insulation oil in transformers, the research on its insulation characteristics had been carried out under severe non- uniform electric field. In this study, the breakdown voltages and propagation velocities of the novel three-element mixed insulation oil under standard lightning impulse voltage were measured by the rising-voltage method, and the oil gap distance was adjusted from 5mm to 25mm. The dissolved gas characteristics after breakdown fault of the novel three-element mixed insulation oil were also studied at gap distance of 10 mm by gas chromatography. Compared the lightning impulse breakdown voltages of the novel three-element mixed insulation oil with that of mineral oil, the former exhibits much lower breakdown voltages under negative polarity than the latter, and slightly higher under positive polarity. The novel three-element mixed insulation oil also has lower propagation velocities than mineral oil at gap distances from 5 mm to 25 mm. Besides, H-2 and C2H2 are the main gaseous products after lightning breakdown fault of the novel three- element mixed insulation oil. With the increase of breakdown times, the contents of H-2 and C2H2 are obviously increased, which can be used as the characteristic gases of lightning impulse breakdown fault for the novel three-element mixed insulation oil.
引用
收藏
页码:526 / 529
页数:4
相关论文
共 50 条
  • [41] Insulation Characteristics and Its Evaluation Method of N2 Gas for Nonstandard Lightning Impulse Waveforms
    Kaneko, Shuhei
    Okabe, Shigemitsu
    ELECTRICAL ENGINEERING IN JAPAN, 2009, 167 (02) : 10 - 20
  • [42] Effect of wave oscillation on breakdown characteristics of oil-impregnated paper under lightning impulse voltage
    Guo, Ruochen
    Wang, Zhen
    Zhang, Xuanrui
    Wu, Jiushan
    Han, Xutao
    Li, Junhao
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 200
  • [43] Differences in Characteristics of Long-Gap Lightning Impulse Breakdown between Vegetable and Mineral Insulating Oil
    Wenxiong Mo
    Haoyong Song
    Qingdan Huang
    Yuqing Chen
    Wei Wang
    Transactions on Electrical and Electronic Materials, 2021, 22 : 301 - 309
  • [44] Interturn insulation characteristics for transformer windings using three ester types under lightning impulse voltage
    Miyagi, Katsunori
    Hanaoka, Ryoichi
    Matsushita, Keiichiro
    Wakimoto, Kiyoshi
    2019 IEEE 20TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2019,
  • [45] Pre-breakdown Streamer Propagation and Breakdown Characteristics of Refined Bleached and Deodorized Palm Oil under Lightning Impulse Voltage
    Thien, Y. V.
    Azis, N.
    Jasni, J.
    Ab Kadir, M. Z. A.
    Yunus, R.
    Jamil, M. K. Mohd
    Yaakub, Z.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (05) : 1614 - 1620
  • [46] Evaluation of Breakdown Characteristics of N2 Gas for Non-standard Lightning Impulse Waveforms - Method for Converting Non-standard Lightning Impulse Waveforms into Standard Lightning Impulse Waveforms
    Wada, Junichi
    Ueta, Genyo
    Okabe, Shigemitsu
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (02) : 505 - 514
  • [47] Evaluation of Breakdown Characteristics of CO2 Gas for Non-standard Lightning Impulse Waveforms - Method for Converting Non-standard Lightning Impulse Waveforms into Standard Lightning Impulse Waveforms
    Ueta, Genyo
    Wada, Junichi
    Okabe, Shigemitsu
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (05) : 1724 - 1733
  • [48] THE ELECTRICAL BREAKDOWN CHARACTERISTICS OF OIL-PAPER INSULATION UNDER STEEP-FRONT IMPULSE VOLTAGES
    VANDERMAAR, AJ
    WANG, M
    NEILSON, JB
    SRIVASTAVA, KD
    IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (04) : 1926 - 1935
  • [49] Discussion on Lightning Impulse Test Waveform According to Breakdown Characteristics of SF6 Gas Gaps
    Wen, Tao
    Zhang, Qiaogen
    Zhang, Lingli
    Ma, Jingtan
    Guo, Can
    Chen, Ming
    Li, Yuan
    Shimomura, Naoyuki
    Chen, Weijiang
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (04) : 2306 - 2313
  • [50] Lightning impulse breakdown characteristics of SF6 alternative gases for gas-insulated switchgear
    Hoshina, Y
    Sato, M
    Shiiki, M
    Hanai, M
    Kaneko, E
    IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 2006, 153 (01) : 1 - 6