Investigation on Lightning Impulse Breakdown and Dissolved Gas Characteristics of the Novel Three-element Mixed Insulation Oil

被引:0
|
作者
Chen Xin [1 ]
Hao Jian [1 ]
Yang Lijun [1 ]
Liu Xiong [2 ]
Liao Ruijin [1 ]
Feng Dawei [1 ]
Wang Qian [2 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400044, Peoples R China
[2] State Grid Chongqing Elect Power Co, Chongqing Elect Power Res Inst, Chongqing 401123, Peoples R China
来源
2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019) | 2019年
关键词
D O I
10.1109/icempe.2019.8727290
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As a kind of potential alternative of traditional mineral insulation oil, mixed oil gives rise to numerous researches on its physicochemical and insulation properties. On this background, a novel three- element mixed insulation oil was developed successfully by our team. Its key parameters meet the requirements of IEC 60296:2012. In order to promote the application of the novel three-element mixed insulation oil in transformers, the research on its insulation characteristics had been carried out under severe non- uniform electric field. In this study, the breakdown voltages and propagation velocities of the novel three-element mixed insulation oil under standard lightning impulse voltage were measured by the rising-voltage method, and the oil gap distance was adjusted from 5mm to 25mm. The dissolved gas characteristics after breakdown fault of the novel three-element mixed insulation oil were also studied at gap distance of 10 mm by gas chromatography. Compared the lightning impulse breakdown voltages of the novel three-element mixed insulation oil with that of mineral oil, the former exhibits much lower breakdown voltages under negative polarity than the latter, and slightly higher under positive polarity. The novel three-element mixed insulation oil also has lower propagation velocities than mineral oil at gap distances from 5 mm to 25 mm. Besides, H-2 and C2H2 are the main gaseous products after lightning breakdown fault of the novel three- element mixed insulation oil. With the increase of breakdown times, the contents of H-2 and C2H2 are obviously increased, which can be used as the characteristic gases of lightning impulse breakdown fault for the novel three-element mixed insulation oil.
引用
收藏
页码:526 / 529
页数:4
相关论文
共 50 条
  • [21] Lightning impulse breakdown characteristics of high-pressure N2 as an alternative insulation gas to SF6
    Goshima, H
    Shinkai, H
    Yashima, M
    GASEOUS DIELECTRICS IX, 2001, : 359 - 364
  • [22] Power frequency breakdown characteristics of new 3-element mixed insulation oil and oil-impregnated pressboard
    Feng, Dawei
    Hao, Jian
    Liao, Ruijin
    Chen, Xin
    Yang, Lijun
    Li, Jian
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (06) : 1885 - 1893
  • [23] Evaluation of breakdown characteristics of oil-immersed transformers under non-standard lightning impulse waveforms - Definition of non-standard lightning impulse waveforms and insulation characteristics for waveforms including pulses
    Okabe, Shigemitsu
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2007, 14 (01) : 146 - 155
  • [24] Breakdown Characteristics of a Transformer Oil in Moderately-Uniform Fields under Lightning Impulse
    Yu, Haichuan
    Liu, Qiang
    Wang, Zhongdong
    Wilkinson, Mark
    Krause, Christoph
    Gyore, Attila
    Hilker, Andree
    2022 IEEE 21ST INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2022,
  • [25] Insulation Characteristics of Gas Insulated Switchgear under Lightning Impulse and AC Superimposed Voltage
    Ueta, Genyo
    Tsuboi, Toshihiro
    Takami, Jun
    Okabe, Shigemitsu
    Ametani, Akihiro
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (03) : 1026 - 1034
  • [26] Turn-to-turn Insulation Breakdown Characteristics Under Non-standard Lightning Impulse Voltages
    Wang, Tonglei
    Li, Yuan
    Wang, Zhe
    Ni, Heli
    Wen, Tao
    Guo, Can
    Gao, Meng
    Qin, Yifan
    Zhang, Qiaogen
    2015 IEEE 11TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, 2015, : 200 - 203
  • [27] Study on the lightning impulse breakdown characteristics of gaseous insulation media for the design of a high voltage superconducting apparatus
    Kang, H.
    Na, J. B.
    Ahn, M. C.
    Bae, D. K.
    Kim, Y. H.
    Ko, T. K.
    PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2010, 470 (20): : 1691 - 1694
  • [28] Breakdown Characteristics of Transformer Oil Insulation under Impulse Voltage with Different Waveform Parameters
    Zhao Tao
    Liu Yunpeng
    Lv Fangcheng
    Cheng Xiangrui
    Wang Zibo
    Wang Fochi
    Xie Qing
    2017 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2017, : 368 - 371
  • [29] Evaluation of Breakdown Characteristics of Gas Insulated Switchgears for Non-standard Lightning Impulse Waveforms - Breakdown Characteristics for Non-standard Lightning Impulse Waveforms under Diverse Conditions
    Okabe, Shigemitsu
    Yuasa, Sadayuki
    Kaneko, Shuhei
    Ueta, Genyo
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (05) : 1415 - 1423
  • [30] Lightning Impulse Breakdown Performance of an Inhibited Gas-To-Liquid (GTL) Hydrocarbon Transformer Oil
    Lu, W.
    Liu, Q.
    Wang, Z. D.
    Smith, P. W. R.
    PROCEEDINGS OF THE 2014 IEEE 18TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL 2014), 2014,