Criteria Revision of Dissolved Gas Analysis for Oil-Filled Transformers in Korea

被引:0
|
作者
Cho, Sung-Min [1 ]
Kim, Jae-Chul [1 ]
机构
[1] Soongsil Univ, Dept Elect Engn, Seoul 156743, South Korea
来源
2009 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-8 | 2009年
关键词
Fault diagnosis; Maintenance; Oil insulation; Power transformers;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The story on revising criteria of Dissolved Gases Analysis (DGA) at KEPCO was introduced. Because of differences in operating environments, construction type, oil volume, and other factors, the interpretative criteria of DGA at KEPCO should be different from other standards such as IEC-60599, or Rogers and Doernenburg. We tried to improve efficiency of DGA by considering accumulated data during twenty-five years. To establish the most appropriate criteria, the DGA results were collected from healthy power transformers as well as transformers which have an incipient fault. The criteria were revised newly using cumulative distribution of concentration of 3,585 healthy power transformers. Although the criteria are revised strictly, work load doesn't increase by controlling analysis interval and condition level.
引用
收藏
页码:4057 / 4060
页数:4
相关论文
共 50 条
  • [1] A Spreadsheet Based Dissolved Gas Analysis Diagnostic Tool For Oil-Filled Transformers
    Mekkayil, Anju
    Pillai, Gobind
    Malcolm, Marc
    2020 55TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC), 2020,
  • [2] Preliminary Results for Dissolved Gas Levels in a Vegetable Oil-Filled Power Transformer
    Martin, Daniel
    Lelekakis, Nick
    Davydov, Valery
    Odarenko, Yuriy
    IEEE ELECTRICAL INSULATION MAGAZINE, 2010, 26 (05) : 41 - 48
  • [3] Acoustic Based Localization of Partial Discharge Inside Oil-Filled Transformers
    Besharatifard, Hamidreza
    Hasanzadeh, Saeed
    Heydarian-Forushani, Ehsan
    Muyeen, S. M.
    IEEE ACCESS, 2022, 10 : 55288 - 55297
  • [4] RMP Neural Network Based Dissolved Gas Analyzer for Fault Diagnostic of Oil-filled Electrical Equipment
    Wu, Huaren
    Li, Xiaohui
    Wu, Danning
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (02) : 495 - 498
  • [5] Condition monitoring of in-service oil-filled transformers: Case studies and experience
    Rao, U. Mohan
    Fofana, I.
    Betie, A.
    Senoussaoui, M. L.
    Brahami, M.
    Briosso, E.
    IEEE ELECTRICAL INSULATION MAGAZINE, 2019, 35 (06) : 33 - 42
  • [6] Fault diagnosis for oil-filled transformers using voting based extreme learning machine
    Zhang, Liwei
    Zhai, Jian
    CLUSTER COMPUTING-THE JOURNAL OF NETWORKS SOFTWARE TOOLS AND APPLICATIONS, 2019, 22 (Suppl 4): : S8363 - S8370
  • [7] Fault diagnosis for oil-filled transformers using voting based extreme learning machine
    Liwei Zhang
    Jian Zhai
    Cluster Computing, 2019, 22 : 8363 - 8370
  • [8] A Review of Dissolved Gas Analysis in Power Transformers
    Sun, Huo-Ching
    Huang, Yann-Chang
    Huang, Chao-Ming
    2011 2ND INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY ENGINEERING (ICAEE), 2012, 14 : 1220 - 1225
  • [9] Assessment of Insulation System State for Oil-Filled High-Voltage Transformers
    Zenova E.V.
    Chernyshev V.A.
    Russian Electrical Engineering, 2019, 90 (02): : 140 - 146
  • [10] REVIEW OF CHEMICAL INDICATORS OF DEGRADATION OF CELLULOSIC ELECTRICAL PAPER INSULATION IN OIL-FILLED TRANSFORMERS
    EMSLEY, AM
    STEVENS, GC
    IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1994, 141 (05) : 324 - 334