Field and laboratory aging of RTV silicone insulator coatings

被引:39
作者
Homma, H [1 ]
Mirley, CL [1 ]
Ronzello, J [1 ]
Boggs, SA [1 ]
机构
[1] Univ Connecticut, Elect Insulat Res Ctr, Storrs, CT 06269 USA
关键词
D O I
10.1109/61.891518
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The silicone-based coating applied to 345 kV post insulators in a substation on the shore of Long Island Sound has depolymerized over a period of about 7 years although no in-service failures have occurred. However, the increasing rate of depolymerization suggests that the coatings will have to be renewed in the near future, This paper reports comparisons of aging and material properties for a number of RTV silicone insulator coatings and measurements related to application of a new coating over an existing, held-aged coating.
引用
收藏
页码:1298 / 1303
页数:6
相关论文
共 7 条
[1]   SURFACE HYDROPHOBICITY OF POLYMERS USED FOR OUTDOOR INSULATION [J].
GORUR, RS ;
CHANG, JW ;
AMBURGEY, OG .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (04) :1923-1933
[2]  
HOMMA H, 1995, P 5 INT C COND BREAK, P575
[3]  
JANSSEN H, 1997, 10 ISH MONTR CAN
[4]   EFFECTS OF FILLER LEVEL IN RTV SILICONE-RUBBER COATINGS USED IN HV INSULATORS [J].
KIM, SH ;
CHERNEY, EA ;
HACKAM, R .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1992, 27 (06) :1065-1072
[5]  
MILLER D, 1993, TECHNICAL REPORT LON
[6]  
Noll W., 1966, CHEM TECHNOLOGY SILI, p[233, 495]
[7]  
WAKE WC, SILOXANE POLYM, P106