Experimental performance analysis of a solar assisted ground source heat pump system under different heating operation modes

被引:128
作者
Dai, Lanhua [1 ]
Li, Sufen [1 ]
Lin DuanMu [2 ]
Li, Xiangli [2 ]
Shang, Yan [1 ]
Dong, Ming [1 ]
机构
[1] Dalian Univ Technol, Minist Educ, Key Lab Ocean Energy Utilizat & Energy Conservat, Dalian 116024, Peoples R China
[2] Dalian Univ Technol, Sch Civil Engn, Dalian 116024, Peoples R China
关键词
Solar; Ground source heat pump; Operation modes; Heating performance; Experimental study; Hybrid energy system; COLLECTORS;
D O I
10.1016/j.applthermaleng.2014.09.061
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents an experimental study on the influence of operation modes on the heating performance of a solar assisted ground source heat pump system (SAGSHPS). Through experiments conducted in January, the characteristics of the SAGSHPS were investigated under different heating operation modes. The results indicate that the solar thermal could be used to accelerate the soil recovery when the heat pump unit is turned off, but the duration of solar use to recharge boreholes should be optimized according to the water temperature in the solar heat storage water tank to avoid unnecessary power consumption of the circulation pump. In addition, the solar heat storage water tank is beneficial for the stable operation of the SAGSHPS. The volumetric flow rate in the water tank has a significant impact on the electricity consumption of the SAGSHPS. From comprehensive analysis of the integral effect of the SAGSHPS under different modes, the mode in which the water tank is connected with the ground heat exchangers (GHES) in series is the recommended mode for the SAGSHPS in the coldest month in Dalian. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:325 / 333
页数:9
相关论文
共 27 条
[1]   Energy analysis of a solar-ground source heat pump system with vertical closed-loop for heating applications [J].
Bakirci, Kadir ;
Ozyurt, Omer ;
Comakli, Kemal ;
Comakli, Omer .
ENERGY, 2011, 36 (05) :3224-3232
[2]   Two years of recorded data for a multisource heat pump system: A performance analysis [J].
Busato, F. ;
Lazzarin, R. M. ;
Noro, M. .
APPLIED THERMAL ENGINEERING, 2013, 57 (1-2) :39-47
[3]   Performance analysis of a proposed solar assisted ground coupled heat pump system [J].
Chen, Xi ;
Yang, Hongxing .
APPLIED ENERGY, 2012, 97 :888-896
[4]   Experimental studies on a ground coupled heat pump with solar thermal collectors for space heating [J].
Chen Xi ;
Yang Hongxing ;
Lu Lin ;
Wang Jinggang ;
Liu Wei .
ENERGY, 2011, 36 (08) :5292-5300
[5]  
Chiasson A.D., 2003, ASHRAE T, V109, P487
[6]  
Fan P.P., 2005, THESIS DALIAN U TECH
[7]   Thermal performance and ground temperature of vertical pile-foundation heat exchangers: A case study [J].
Gao, Jun ;
Zhang, Xu ;
Liu, Jun ;
Li, Kui Shan ;
Yang, Jie .
APPLIED THERMAL ENGINEERING, 2008, 28 (17-18) :2295-2304
[8]   Optimization of systems with the combination of ground-source heat pump and solar collectors in dwellings [J].
Kjellsson, Elisabeth ;
Hellstrom, Goran ;
Perers, Bengt .
ENERGY, 2010, 35 (06) :2667-2673
[9]   Dual source heat pump systems: Operation and performance [J].
Lazzarin, Renato M. .
ENERGY AND BUILDINGS, 2012, 52 :77-85
[10]   Soil temperature distribution around a U-tube heat exchanger in a multi-function ground source heat pump system [J].
Li, Shuhong ;
Yang, Weihua ;
Zhang, Xiaosong .
APPLIED THERMAL ENGINEERING, 2009, 29 (17-18) :3679-3686