Experimental study of a natural draft hybrid (wet/dry) cooling tower with a splash fill type

被引:0
作者
Ali, Abdullah Kadhlm [1 ]
Mohammed, Ahmed Qassem [1 ]
Mahdi, Qasim Selah [2 ]
机构
[1] Middle Tech Univ, Engn Tech Coll, Mech Eng Dept IRAQ, Baghdad, Iraq
[2] Mustansiriyah Univ, Mech Engn Dept IRAQ, Coll Engn, Baghdad, Iraq
关键词
cooling range; wet bulb temperature; cooling tower; performance factors; air velocity; splash fill type; heat exchanger; ARTIFICIAL NEURAL-NETWORK; CROSS-WIND; COUNTER-FLOW; PERFORMANCE;
D O I
10.3934/energy.2022031
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Cooling towers have such a significant influence on work and efficiency that researchers and designers are working tirelessly to enhance their performance. A prototype design for a natural draft hybrid (wet/dry) cooling tower has been created, relying on geometrical, dynamic, and thermodynamic similarities. Based on Iraqi weather, experiments have been conducted using splash fill (150 mm) in summer (hot and dry) weather conditions. This study investigated heat transfer mechanisms of both air and water in a natural draft hybrid cooling tower model(NDHCTs), both directly (wet section) and indirectly (dry section). The tower is filled with splash-style packing, and the warm water is spread throughout the building using sprayer nozzles. The influences of water flow rates, fill thickness, and air velocity on the cooling range, approach, cooling capacity, thermal efficiency of the cooling tower, water evaporation loss into the air stream and water loss percentage were explored in this study. The experimental were carried out with four different water flow rates, ranging from 7.5 to 12 (Lpm) litres per minute, and eight different air velocities, all while keeping a constant inlet water temperature and a zero (m/s) crosswind. Data has been gathered, and performance variables have been determined. The findings demonstrate that the cooling tower's efficacy increases when the water flow rate is low, and the cooling range increases with increasing air velocity and decreases with increasing water flow rate; for a 7.5 Lpm water flow rate and a 2.4 m/s air velocity, it expanded to 19.5 degrees C. The cooling capacity increased to 23.2 kW for a water flow rate of 12 Lpm and an air velocity of 2.4 m/s.
引用
收藏
页码:648 / 664
页数:17
相关论文
共 22 条
[1]   The performance of natural draft dry cooling towers under crosswind: CFD study [J].
Al-Waked, R ;
Behnia, M .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2004, 28 (02) :147-161
[2]   Experimental investigation of the performance of a counter-flow, packed-bed mechanical cooling tower [J].
Bedekar, SV ;
Nithiarasu, P ;
Seetharamu, KN .
ENERGY, 1998, 23 (11) :943-947
[3]  
Dewanjee S, 2020, J ENG RES REPORTS, P41, DOI [10.9734/jerr/2020/v16i217165, DOI 10.9734/JERR/2020/V16I217165]
[4]   Experimental research of heat transfer performance on natural draft counter flow wet cooling tower under cross-wind conditions [J].
Gao, Ming ;
Sun, Feng-zhong ;
Wang, Kai ;
Shi, Yue-tao ;
Zhao, Yuan-bin .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2008, 47 (07) :935-941
[5]   Artificial neural network model research on effects of cross-wind to performance parameters of wet cooling tower based on level Froude number [J].
Gao, Ming ;
Shi, Yue-tao ;
Wang, Ni-ni ;
Zhao, Yuan-bin ;
Sun, Feng-zhong .
APPLIED THERMAL ENGINEERING, 2013, 51 (1-2) :1226-1234
[6]   Performance prediction of wet cooling tower using artificial neural network under cross-wind conditions [J].
Gao, Ming ;
Sun, Feng-zhong ;
Zhou, Shou-jun ;
Shi, Yue-tao ;
Zhao, Yuan-bin ;
Wang, Nai-hua .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2009, 48 (03) :583-589
[7]  
Ghoddousi S, 2021, EUR J SUSTAIN DEV RE, V5, DOI [10.21601/ejosdr/10952, DOI 10.21601/EJOSDR/10952]
[8]  
Gould P.L., 1999, Cooling Tower Structures, Structural Engineering Handbook
[9]   Performance characteristics of a trickle fill in cross- and counter-flow configuration in a wet-cooling tower [J].
Grobbelaar, P. J. ;
Reuter, H. C. R. ;
Bertrand, T. P. .
APPLIED THERMAL ENGINEERING, 2013, 50 (01) :475-484
[10]  
He S., 2015, PERFORMANCE IMPROVEM