Experimental investigation on dynamic performance of air-source heat pump water heater using R134a

被引:2
|
作者
Wang, Zhihua [1 ]
Wang, Fenghao [1 ]
Wu, Xiaozhou [1 ]
Tian, Chun [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Human Settlements & Civil Engn, Xian 710049, Shannxi, Peoples R China
关键词
heat pump water heater; refrigerant charge; TXV opening; thermal expansion valve; dynamic performance; exergetic efficiency; COMPRESSION REFRIGERATION SYSTEM; EXERGY ANALYSIS; EXCHANGER; DRIVEN; ENERGY; R22;
D O I
10.1504/IJEX.2016.075624
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper describes the experiment carried out to analyse the effects of improper refrigerant charge and incorrect thermal expansion valve (TXV) opening on the ASHPWH using R134a. The performance of the system were measured in combinations of four refrigerant charges of 70%, 85%, 100% and 115% of the optimal value and three TXV opening of 30%, 45% and 60% of full opening at ambient temperature of 20 degrees C D/15 degrees C W (dry-bulb temperature/wet-bulb temperature). The results showed that the maximum coefficient of performances (COPs) were nearly 33%, 31.9% and 4.4% higher than that of 70%, 85% and 115% of the optimal refrigerant charge at 60% TXV opening, respectively. And it was found that the increase in TXV opening can enhance the COP when water temperature exceeded 30 degrees C. Besides, an exergy analysis was conducted to evaluate the thermodynamic performance of the system and components in this study.
引用
收藏
页码:276 / 294
页数:19
相关论文
共 50 条
  • [1] Performance comparison of air-source heat pump water heater with different expansion devices
    Peng, Jing-Wei
    Li, Hui
    Zhang, Chun-Lu
    APPLIED THERMAL ENGINEERING, 2016, 99 : 1190 - 1200
  • [2] EXPERIMENTAL RESEARCH ON DYNAMIC PERFORMANCE OF AN AIR/WATER SOURCE HEAT PUMP WATER HEATER
    Qiu, Fuqiang
    Du, Juanli
    Wang, Yu
    Zhang, Xingwei
    Yu, Changsuo
    Nan, Yun
    THERMAL SCIENCE, 2024, 28 (3A): : 2067 - 2074
  • [3] Annual performance analysis of an air source heat pump water heater using a new eco-friendly refrigerant mixture as an alternative to R134a
    Xiao, Biao
    Chang, Huawei
    He, Lin
    Zhao, Shunan
    Shu, Shuiming
    RENEWABLE ENERGY, 2020, 147 (147) : 2013 - 2023
  • [4] Dynamic simulation of an air-source heat pump water heater using novel modified evaporator model
    Chen, Jiaheng
    Yu, Jianlin
    APPLIED THERMAL ENGINEERING, 2018, 144 : 469 - 478
  • [5] AN EXPERIMENTAL ANALYSIS OF AIR SOURCE HEAT PUMP WATER HEATER
    Ozturk, M. Mete
    Erbay, L. Berrin
    ISI BILIMI VE TEKNIGI DERGISI-JOURNAL OF THERMAL SCIENCE AND TECHNOLOGY, 2012, 32 (01) : 117 - 127
  • [6] Comparative experimental analysis of direct-expansion solar-assisted heat pump water heaters using R134a and R290
    Kong, Xiangqiang
    Zhang, Maoyuan
    Yang, Yimeng
    Li, Ying
    Wang, Dechang
    SOLAR ENERGY, 2020, 203 : 187 - 196
  • [7] Performance comparison between the combined R134a/CO2 heat pump and cascade R134a/CO2 heat pump for space heating
    Song, Yulong
    Li, Dongzhe
    Yang, Dongfang
    Jin, Lei
    Cao, Feng
    Wang, Xiaolin
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 74 : 592 - 605
  • [8] The evaluation of the optimal medium temperature in a space heating used transcritical air-source CO2 heat pump with an R134a subcooling device
    Song, Yulong
    Cao, Feng
    ENERGY CONVERSION AND MANAGEMENT, 2018, 166 : 409 - 423
  • [9] Experimental Investigation on an Ultra-High Temperature Air Source Heat Pump Water Heater
    Xu, Yu
    Zhu, Zihang
    Fu, Chunda
    Xia, Wenqing
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2021, 13 (06)
  • [10] A prediction model of air-source heat pump system performance with frost-retarded heater
    Wu, Siyuan
    Sun, Yu
    Wang, Fei
    Ma, Zhiheng
    Zhao, Rijing
    Huang, Dong
    APPLIED THERMAL ENGINEERING, 2024, 248