An underfrequency load shedding scheme for high dependability and security tolerant to induction motors dynamics

被引:6
作者
Maresch, K. [1 ]
Marchesan, G. [2 ]
Cardoso Junior, G. [3 ]
Borges, Adriano [3 ]
机构
[1] Univ Fed Santa Maria UFSM, Programa Posgrad Engn Eletr PPGEE, Ctr Excelencia Energia & Sistemas Potencia CEESP, Lab Anal & Protecao Sistemas Eletr LAPES, Santa Maria, RS, Brazil
[2] Univ Fed Santa Maria, PPGEE, Dept Eletromecan & Sistemas Potencia DESP, CEESP,LAPES, Santa Maria, RS, Brazil
[3] Univ Fed Santa Maria, DESP, CEESP, LAPES, Santa Maria, RS, Brazil
关键词
Under-frequency load shedding; Induction motor dynamics; Discriminant functions analysis;
D O I
10.1016/j.epsr.2021.107217
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The load shedding scheme is a last resort to prevent power system collapse when the available generation is less than the load demand. The traditional load shedding schemes monitors the frequency and voltage by underfrequency and undervoltage relays and provides load cutoff until the frequency returns to a stable point of operation. The reduction of rotating inertia demands faster load shedding to meet the stability requirements. In some electrical power systems in Brazil, it was found that, in the event of opening a transmission line upstream of the load shedding substation, some under frequency relay may operate improperly. This paper proposes a new method to avoid the unwanted operation of load shedding schemes when the utility substation (source) is out of service. The proposed method monitors negative sequence voltage, frequency and its rate of change, enabling faster load shedding (high dependability) without unwanted (high security) operation when compared with traditional methods. Events were classified by linear discriminant analysis and tested in the IEEE 9 bus test system. The tests consisted of several disturbances such as loss of generation and line outages at different levels of feeder loading, reactive compensation and distributed generation. The proposed method reached a 100% rate of correct classification.
引用
收藏
页数:8
相关论文
共 22 条
[1]  
Alpaydin E, 2014, ADAPT COMPUT MACH LE, P1
[2]  
Anderson P.M., 2003, Power System Control and Stability
[3]   Under voltage load shedding in power systems with wind turbine-driven doubly fed induction generators [J].
Arief, Ardiaty ;
Dong, ZhaoYang ;
Nappu, Muhammad Bachtiar ;
Gallagher, Marcus .
ELECTRIC POWER SYSTEMS RESEARCH, 2013, 96 :91-100
[4]   Undervoltage load shedding for induction motor dominant loads considering P,Q coupling [J].
Balanathan, R ;
Pahalawaththa, NC ;
Annakkage, UD .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1999, 146 (04) :337-342
[5]   Semi-Adaptive Setting of Under Frequency Load Shedding Relays Considering Credible Generation Outage Scenarios [J].
Banijamali, Seyed Sohrab ;
Amraee, Turaj .
IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (03) :1098-1108
[6]   A Study on a Centralized Under-Voltage Load Shedding Scheme Considering the Load Characteristics [J].
Deng, Jiyu ;
Liu, Junyong .
INTERNATIONAL CONFERENCE ON APPLIED PHYSICS AND INDUSTRIAL ENGINEERING 2012, PT A, 2012, 24 :481-489
[7]  
Duda R, 2000, PATTERN CLASSIFICATI
[8]   Load shedding: A new proposal [J].
Faranda, Roberto ;
Pievatolo, Antonio ;
Tironi, Enrico .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (04) :2086-2093
[9]   REGULARIZED DISCRIMINANT-ANALYSIS [J].
FRIEDMAN, JH .
JOURNAL OF THE AMERICAN STATISTICAL ASSOCIATION, 1989, 84 (405) :165-175
[10]  
Guo B.Y, 2005, BIOESTATISTICS