Partial discharge measurements on hydro generator stator windings case studies

被引:8
|
作者
Li, Shunyuan [1 ]
Chow, Jennifer M. Y. [1 ]
机构
[1] British Columbia Hydro & Power Author, Vancouver, BC, Canada
关键词
partial discharge (PD); pulse phase analysis; PD patterns; generator stator windings; groundwall insulation; end winding;
D O I
10.1109/MEI.2007.369456
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
An overview is given of four case studies of four dominant partial discharge (PD) activity types in generator stator windings, including measurements and data analysis. The PD analysis considered the PD pattern, polarity dominance, and pulse phase analysis (PPA) in correlation with visual inspections and high-voltage testing. The four PD cases are as follows: PD within the groundwall insulation, confirmed by conducting dissipation factor tip-up and corona probe tests; PD at the end of a slot, confirmed by removing the bars from the slot; PD at winding end-turns, confirmed through a blackout test and visual inspection; and PD at the stress control grading paint area, confirmed by visual inspections.
引用
收藏
页码:5 / 15
页数:11
相关论文
共 50 条
  • [21] Investigation of the effect of humidity on partial discharge activity in stator windings
    Fenger, M
    Stone, GC
    PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2003, : 1080 - 1083
  • [22] Effects of Frequency and Temperature on Partial Discharge Characterization of Stator Windings
    Kantar, Emre
    Eberg, Espen
    Hvidsten, Sverre
    2020 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (2020 IEEE CEIDP), 2020, : 369 - 373
  • [23] Propagation of partial discharge signals in stator windings of turbine generators
    Pemen, AJM
    van der Laan, PCT
    de Leeuw, W
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2006, 21 (01) : 155 - 161
  • [24] Relative Ability of UHF Antenna and VHF Capacitor Methods to Detect Partial Discharge in Turbine Generator Stator Windings
    Stone, G. C.
    Chan, C.
    Sedding, H. G.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (06) : 3069 - 3078
  • [25] Using partial discharge measurement technology to implement predictive maintenance in high voltage motor and generator stator windings
    Stone, G
    Kapler, J
    1997 IEEE/PCA CEMENT INDUSTRY TECHNICAL CONFERENCE - XXXIX CONFERENCE RECORD, 1997, : 63 - 68
  • [26] Travelling wave propagation of partial discharges along generator stator windings
    Su, Q
    Chang, C
    Tychsen, RC
    PROCEEDINGS OF THE 5TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 1997, : 1132 - 1135
  • [27] Influence of mechanical vibration on the behavior of partial discharges in generator stator windings
    Wu, K
    Kanegami, M
    Takahashi, T
    Suzuki, H
    Ito, T
    Okamoto, T
    Yano, H
    Proceedings of the 2005 International Symposium on Electrical Insulating Materials, Vols, 1-3, 2005, : 281 - 284
  • [28] Online Partial Discharge Measurements in an Operating Generator Stator Winding Using UHF Antennas
    Partyka, Mike
    Bridges, Greg E.
    Kordi, Behzad
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (03) : 1593 - 1602
  • [29] Measurement and analysis of partial discharge in high voltage motor stator windings
    Kim, HD
    Ju, YH
    PROCEEDINGS: ELECTRICAL INSULATION CONFERENCE AND ELECTRICAL MANUFACTURING & COIL WINDING TECHNOLOGY CONFERENCE, 2003, : 27 - 31
  • [30] Surface partial discharge in hydrogenerator stator windings: Causes, symptoms, and remedies
    Dehlinger, Nicolas
    Stone, Greg
    IEEE ELECTRICAL INSULATION MAGAZINE, 2020, 36 (03) : 7 - 18