Fault detection and diagnosis based on improved PCA with JAA method in VAV systems

被引:85
|
作者
Du, Zhimin [1 ]
Jin, Xinqiao [1 ]
Wu, Lizhou [1 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Mech Engn, Shanghai 200030, Peoples R China
关键词
VAV systems; fault characteristic; principal component analysis; joint angle analysis; sensor; fixed and drifting biases;
D O I
10.1016/j.buildenv.2006.08.011
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this paper, improved principal component analysis (PCA) with joint angle analysis (JAA) is presented to detect and diagnose both fixed and drifting biases of sensors in variable air volume (VAV) systems. Fault characteristic concerned in PID controller in the VAV systems is analyzed and discussed. The squared prediction error (SPE) plot based on PCA is used to detect the sensor fixed and drifting biases. Then the JAA plot instead of conventional contribution plot is used to diagnose the faults. And they are tested and evaluated online in a simulated centralized VAV air-conditioning systems. (c) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:3221 / 3232
页数:12
相关论文
共 50 条
  • [21] Fault diagnosis based on PCA for sensors of laboratorial wastewater treatment process
    Tao, E. P.
    Shen, W. H.
    Liu, T. L.
    Chen, X. Q.
    CHEMOMETRICS AND INTELLIGENT LABORATORY SYSTEMS, 2013, 128 : 49 - 55
  • [22] Sensor fault detection and validation of VAV terminals in air conditioning systems
    Wang, SW
    Qin, JY
    ENERGY CONVERSION AND MANAGEMENT, 2005, 46 (15-16) : 2482 - 2500
  • [23] Fault Diagnosis Method of Forging Press Based on Improved CNN
    Yuan, Chao
    Ling, Yunhan
    Zhang, Nan
    Yang, Yong
    Pan, Lidong
    Han, Chong
    Cao, Yeyingnan
    Zhang, Hao
    Nie, Peng
    Ma, Hui
    IEEE ACCESS, 2024, 12 : 181925 - 181936
  • [24] Improved PCA with optimized sensor locations for process monitoring and fault diagnosis
    Wang, HQ
    Song, ZH
    Li, P
    PROCEEDINGS OF THE 39TH IEEE CONFERENCE ON DECISION AND CONTROL, VOLS 1-5, 2000, : 4353 - 4358
  • [25] A statistical training data cleaning strategy for the PCA-based chiller sensor fault detection, diagnosis and data reconstruction method
    Hu, Yunpeng
    Chen, Huanxin
    Li, Guannan
    Li, Haorong
    Xu, Rongji
    Li, Jiong
    ENERGY AND BUILDINGS, 2016, 112 : 270 - 278
  • [26] A Novel Intrusion Detection Method Based on Improved SVM by Combining PCA and PSO
    WANG Hui1
    2.Department of Energy Technology and Mechanical Engineering
    Wuhan University Journal of Natural Sciences, 2011, 16 (05) : 409 - 413
  • [27] PCA-based method of soft fault detection and identification for the ongoing commissioning of chillers
    Cotrufo, Nunzio
    Zmeureanu, Radu
    ENERGY AND BUILDINGS, 2016, 130 : 443 - 452
  • [28] Whole Building System Fault Detection Based on Weather Pattern Matching and PCA Method
    Chen, Yimin
    Wen, Jin
    CONFERENCE PROCEEDINGS OF 2017 3RD IEEE INTERNATIONAL CONFERENCE ON CONTROL SCIENCE AND SYSTEMS ENGINEERING (ICCSSE), 2017, : 728 - 732
  • [29] Data-Driven Fault Detection in Reciprocating Compressors: A Method Based on PCA and GLRT
    Cabrera, Mauricio
    Cabrera, Diego
    Cerrada, Mariela
    Sanchez, Rene-Vinicio
    IFAC PAPERSONLINE, 2024, 58 (08): : 264 - 269
  • [30] Fault detection and diagnosis strategy based on a weighted and combined index in the residual subspace associated with PCA
    Zhang, Cheng
    Gao, Xianwen
    Xu, Tao
    Li, Yuan
    Pang, Yujun
    JOURNAL OF CHEMOMETRICS, 2018, 32 (11)