Annual Assessment of Large-Scale Introduction of Renewable Energy: Modeling of Unit Commitment Schedule for Thermal Power Generators and Pumped Storages

被引:24
作者
Mitani, Takashi [1 ]
Aziz, Muhammad [1 ]
Oda, Takuya [1 ]
Uetsuji, Atsuki [1 ]
Watanabe, Yoko [1 ]
Kashiwagi, Takao [1 ]
机构
[1] Tokyo Inst Technol, Inst Innovat Res, Tokyo 1528550, Japan
关键词
unit commitment; annual analysis; thermal power generator; pumped storage; Tabu search; interior point method; SYSTEM; JAPAN;
D O I
10.3390/en10060738
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The fast-increasing introduction of renewable energy sources (RESes) leads to some problems in electrical power network due to fluctuating generated power. A power system must be operated with provision of various reserve powers like governor free capacity, load frequency control and spinning reserve. Therefore, the generator's schedule (unit commitment schedule) should include the consideration of the various power reserves. In addition, it is necessary to calculate the annual operational costs of electric power systems by solving the unit commitment per week of thermal power generators and pumped storages in order to compare and examine the variance of the operational costs and the operating ratio of the generators throughout the year. This study proposes a novel annual analysis for the thermal power generator and pumped storages under a massive introduction of RESes. A weekly unit commitment schedule (start/stop planning) for thermal power generator and pumped storages has been modeled and calculated for one year evaluation. To solve the generator start/stop planning problem, Tabu search and interior point methods are adopted to solve the operation planning for thermal power generators and the output decision for pumped storages, respectively. It is demonstrated that the proposed method can analyze a one-year evaluation within practical time. In addition, by assuming load frequency control (LFC) constraints to cope with photovoltaic (PV) output fluctuations, the impact of the intensity of LFC constraints on the operational cost of the thermal power generator has been elucidated. The increment of the operational cost of the power supply with increasing PV introduction amount has been shown in concrete terms.
引用
收藏
页数:19
相关论文
共 25 条
  • [1] Optimal Weekly Operation Scheduling of Pumped Storage Hydropower Plant Considering Optimal Hot Reserve Capacity in a Power System with a Large Penetration of Photovoltaic Generation
    Aihara, Ryota
    Yokoyama, Akihiko
    [J]. ELECTRICAL ENGINEERING IN JAPAN, 2016, 195 (02) : 35 - 48
  • [2] Ashina S., 2008, J JPN SOC ENERGY RES, V29, P1
  • [3] Energy conservative brown coal conversion to hydrogen and power based on enhanced process integration: Integrated drying, coal direct chemical looping, combined cycle and hydrogenation
    Aziz, Muhammad
    Zaini, Ilman Nuran
    Oda, Takuya
    Morihara, Atsushi
    Kashiwagi, Takao
    [J]. INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2017, 42 (05) : 2904 - 2913
  • [4] Clean Co-production of H2 and power from low rank coal
    Aziz, Muhammad
    Juangsa, Firman Bagja
    Kurniawan, Winarto
    Budiman, Bentang Arief
    [J]. ENERGY, 2016, 116 : 489 - 497
  • [5] Utilization of Electric Vehicles and Their Used Batteries for Peak-Load Shifting
    Aziz, Muhammad
    Oda, Takuya
    Mitani, Takashi
    Watanabe, Yoko
    Kashiwagi, Takao
    [J]. ENERGIES, 2015, 8 (05) : 3720 - 3738
  • [7] A review of pumped hydro energy storage development in significant international electricity markets
    Barbour, Edward
    Wilson, I. A. Grant
    Radcliffe, Jonathan
    Ding, Yulong
    Li, Yongliang
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 61 : 421 - 432
  • [8] Experiments with the interior-point method for solving large scale Optimal Power Flow problems
    Capitanescu, Florin
    Wehenkel, Louis
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2013, 95 : 276 - 283
  • [9] Experimental performance assessment of an online energy management strategy for varying renewable power production suppression
    Erdinc, O.
    Elma, O.
    Uzunoglu, M.
    Selamogullari, U. S.
    Vural, B.
    Ugur, E.
    Boynuegri, A. R.
    Dusmez, S.
    [J]. INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2012, 37 (06) : 4737 - 4748
  • [10] Komiyama R., 2014, IEEJ T PE, V134, P885, DOI DOI 10.1541/IEEJPES.134.885