Heat source shifting in buildings supplied by district heating and exhaust air heat pump

被引:11
作者
Kensby, J. [1 ]
Truschel, A. [1 ]
Dalenback, J. O. [1 ]
机构
[1] Chalmers, SE-41296 Gothenburg, Sweden
来源
15TH INTERNATIONAL SYMPOSIUM ON DISTRICT HEATING AND COOLING (DHC15-2016) | 2017年 / 116卷
关键词
Heat source shifting; Exhaust air heat pump; District heating; Hourly pricing;
D O I
10.1016/j.egypro.2017.05.094
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The heat supply for Swedish multi-family residential buildings is becoming more complex, and today it is fairly common to combine district heating with a second heat source. The most common heat source to combine with district heating in Sweden is an exhaust air heat pump. On average, the exhaust air heat pump covers 31% of the yearly heat load and is given full load priority. There is a missed potential in cost and CO2 savings when one heat source is given full load priority, since marginal production costs and CO2 emissions constantly vary in both the electrical grid and the district heating system. The aim of this study is to evaluate how buildings with several heat sources should be operated using hourly energy prices. Hourly heat and electricity prices for Gothenburg have been established for two years based on the marginal costs of heat and electricity generation. These prices have been used to evaluate the most common combinations of heat sources. Results show that the most common combination with an exhaust air heat pump with full load priority does not lower costs compared to the reference case with only district heating. However, having a control system that allows heat source shifting and gives load priority to the heat source with the lowest cost each hour can greatly reduce the heating cost, and systems with larger heat pumps show even greater potential for heat source shifting. (C) 2017 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:470 / 480
页数:11
相关论文
共 14 条
  • [1] Boverket, 2017, LAG PA BOST RIK
  • [2] Frederiksen S, 2013, DISTRICT HEATING COO
  • [3] IEA, 2012, EN BAL SWED 2012
  • [4] JOHANSSON C., 2010, 1 AGENT TECHNOLOGY E
  • [5] Energy performance certificates and 3-dimensional city models as a means to reach national targets - A case study of the city of Kiruna
    Johansson, Tim
    Vesterlund, Mattias
    Olofsson, Thomas
    Dahl, Jan
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2016, 116 : 42 - 57
  • [6] Karkkainen A., 2010, FAKULTETEN INGENJORS
  • [7] Kensby J., BUILDINGS THERMAL EN
  • [8] Kensby J, 2014, 14 INT S DISTR HEAT
  • [9] Potential of residential buildings as thermal energy storage in district heating systems - Results from a pilot test
    Kensby, Johan
    Truschel, Anders
    Dalenback, Jan-Olof
    [J]. APPLIED ENERGY, 2015, 137 : 773 - 781
  • [10] Heating system return temperature effect on heat pump performance
    Maivel, Mikk
    Kurnitski, Jarek
    [J]. ENERGY AND BUILDINGS, 2015, 94 : 71 - 79