Experimental evaluation of transcritical CO2 refrigeration with mechanical subcooling

被引:28
作者
Bush, John [1 ]
Beshr, Mohamed [2 ]
Aute, Vikrant [2 ]
Radermacher, Reinhard [2 ]
机构
[1] Elect Power Res Inst, 942 Corridor Pk Blvd, Knoxville, TN 37932 USA
[2] Univ Maryland, Ctr Environm Energy Engn, College Pk, MD 20742 USA
关键词
SUPERMARKET REFRIGERATION; PERFORMANCE; COMPRESSION; SYSTEMS; ENERGY; CYCLE; CONFIGURATIONS; MODEL;
D O I
10.1080/23744731.2017.1289056
中图分类号
O414.1 [热力学];
学科分类号
摘要
Transcritical CO2 booster refrigeration systems have seen a growing interest in recent years as they can provide two-stage refrigeration with R744, which has a global warming potential of 1.0, as the working fluid. However, the efficiency of these systems, particularly in transcritical operation, is often not as good as the efficiency of comparable conventional equipment. One possible way to improve performance in hot climates is through the use of a mechanical subcooler. This study describes laboratory testing of a lab-scale transcritical booster system, with and without mechanical subcooling and in transcritical and subcritical operating modes. In addition, a new steady-state model for generalized vapor compression systems was developed and is presented here. The model is used to simulate the system tested in the current article. The testing showed a significant improvement in both capacity and efficiency at all operating conditions with the subcooler. The solver was able to match capacity, power, and efficiency to within 3% for all test conditions. The model was used to perform a parametric study of subcooler capacity on the cycle; the results show that added subcooling substantially improves overall coefficient of performance and reduces the need for bypass flow, but the overall coefficient of performance benefit diminishes as the efficiency of the main cycle increases.
引用
收藏
页码:1013 / 1025
页数:13
相关论文
共 29 条
[1]  
[Anonymous], 12 IIR G LOR NAT WOR
[2]  
[Anonymous], 12 IIR G LOR NAT WOR
[3]  
ANSI/AHRI, 2015, 5402015 ANSIAHRI ASH
[4]   Theoretical performance of tratiscritical carbon dioxide cycle with two-stage compression and intercooling [J].
Baek, JS ;
Groll, EA ;
Lawless, B .
PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART E-JOURNAL OF PROCESS MECHANICAL ENGINEERING, 2005, 219 (E2) :187-195
[5]  
Beshr M., 2016, THESIS
[6]   Condensation in horizontal smooth tubes: A new heat transfer model for heat exchanger design [J].
Cavallini, Alberto ;
Del Col, Davide ;
Doretti, Luca ;
Matkovic, Marko ;
Rossetto, Luisa ;
Zilio, Claudio ;
Censi, Giuseppe .
HEAT TRANSFER ENGINEERING, 2006, 27 (08) :31-38
[7]  
Dang C., 2003, Trans. JSRAE, V120, P175
[8]   Particular characteristics of transcritical CO2 refrigeration cycle with an ejector [J].
Deng, Jian-qiang ;
Jiang, Pei-xue ;
Lu, Tao ;
Lu, Wei .
APPLIED THERMAL ENGINEERING, 2007, 27 (2-3) :381-388
[9]  
Eikevik T., 2016, 12 IIR GUST LOR NAT
[10]   Thermodynamic analysis of transcritical CO2 booster refrigeration systems in supermarket [J].
Ge, Y. T. ;
Tassou, S. A. .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (04) :1868-1875