Optimal Design of a Medium Voltage Hybrid Fault Current Limiter

被引:0
作者
Magnusson, Jesper [1 ]
Martinez-Velasco, Juan A. [2 ]
Bissal, Ara [1 ]
Engdahl, Goran [1 ]
Liljestrand, Lars
机构
[1] Royal Inst Technol KTH, Dept Electromagnet Engn, Tekn Ringen 33, S-10044 Stockholm, Sweden
[2] Univ Politecn Cataluna, ETSEIB, Dept Enginyeria Elect, E-08028U Barcelona, Spain
来源
2014 IEEE INTERNATIONAL ENERGY CONFERENCE (ENERGYCON 2014) | 2014年
关键词
Fault current limiter; hybrid switch; modelling; optimization; power systems; transient analysis;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The connection of distributed generation increases the short circuit power which in turn might exceed the ratings of the installed circuit breakers. A solution is to limit the available short circuit power by increasing the grid impedance, but since there is a constant strive for lower losses and higher power transfer capabilities, this is not desired. The application of a fault current limiter (FCL) that can limit the current before the first peak enables a power system with high short circuit power and low short circuit current. This can increase the stability of the grid and reduce the requirements of other equipment. This work presents a simulation model to be used as an aid in the design of a hybrid FCL for a 12 kV AC system. The proposed model combines a transient analysis circuit model with an optimization module to obtain multiple sets of possible design parameters. The design is not straight forward since there is a trade-off between several of the design parameters.