Development of a steady-state physical-based mathematical model for a direct expansion based enhanced dehumidification air conditioning system

被引:18
作者
Chen, Wenjing [1 ]
Chan, Ming-yin [1 ]
Weng, Wenbing [2 ]
Yan, Huaxia [3 ]
Deng, Shiming [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China
[2] Univ Shanghai Sci & Technol, Sch Environm & Architecture, Shanghai, Peoples R China
[3] Technol & Higher Educ Inst Hong Kong, Fac Sci & Technol, Hong Kong, Hong Kong, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2018年 / 91卷
关键词
Direct expansion; Air conditioning; Enhanced dehumidification; Mathematical model; Experimental validation; INHERENT OPERATIONAL CHARACTERISTICS; FUZZY-LOGIC CONTROLLER; VARIABLE-SPEED; HUMIDITY CONTROL; A/C SYSTEM; TEMPERATURE; PERFORMANCE; UNIT;
D O I
10.1016/j.ijrefrig.2018.04.028
中图分类号
O414.1 [热力学];
学科分类号
摘要
It is challenging and difficult for a conventional On-Off controlled single evaporator direct expansion (DX) air conditioning (A/C) system to deal with the variable latent load, unless complicated and costly supplementary measures to supply variable dehumidification ability are provided. Therefore, based on multi-evaporator air conditioning technology, a standalone DX based enhanced dehumidification air conditioning (EDAC) system with two evaporators was proposed to provide variable dehumidification ability. This paper reports on the development of a steady-state physical-based mathematical model for such an EDAC system. Firstly, a detailed description on the configuration of the EDAC system is presented, followed by reporting the development and experimental validation of the steady-state model for EDAC system. Thirdly, using the validated EDAC model, a follow-up detailed modeling study was carried out to both demonstrate that the EDAC system was able to provide variable dehumidification ability and optimize the sizing of the two evaporators used in the EDAC system. The modeling study results indicated that the EDAC system could produce variable dehumidification capacity. The modeling study results also suggested that a lower ratio of surface areas for the two evaporators in an EDAC system was beneficial to enlarging its variation ranges of both total cooling capacity (TCC) and equipment sensible heat ratio (E SHR). (C) 2018 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:55 / 68
页数:14
相关论文
共 32 条
[1]  
[Anonymous], 2009, ASHRAE Fundamentals 2009
[2]  
[Anonymous], 2006, UNDERSTANDING DEHUMI, DOI DOI 10.2172/881342
[3]  
ASHRAE, 1986, ASHRAE Standard 41.1: Standard Method for Temperature Measurement
[4]  
ASHRAE, 1987, ASHRAE Standard 41.2-Standard methods for laboratory air-flow measurement
[5]  
ASHRAE, 2008, HVAC SYST EQ, P1
[6]  
Berglund LG, 1998, ASHRAE J, V40, P35
[7]   Stepped pressure cycle - A new approach to Lorenz cycle [J].
Cao, Xiang ;
Zhang, Chun-Lu ;
Zhang, Zi-Yang .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 74 :283-294
[8]   Development of a dynamic model for a DX VAV air conditioning system [J].
Chen, Wu ;
Deng, Shiming .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (18-19) :2900-2924
[9]   Operational experiences with solar air collector driven desiccant cooling systems [J].
Eicker, Ursula ;
Schneider, Dietrich ;
Schumacher, Juergen ;
Ge, Tianshu ;
Dai, Yanjun .
APPLIED ENERGY, 2010, 87 (12) :3735-3747
[10]   Potential energy benefits of integrated refrigeration system with microturbine and absorption chiller [J].
Hwang, YH .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (08) :816-829