Harmonic Disturbance Control in Islanded Smart Grids

被引:0
|
作者
Lamedica, Regina [1 ]
Maccioni, Marco [1 ]
Ruvio, Alessandro [1 ]
Geri, Alberto [1 ]
Gatta, Fabio Massimo [1 ]
机构
[1] Sapienza Univ Rome, Dept Astronaut Elect & Energy Engn DIAEE, Rome, Italy
来源
2018 INTERNATIONAL SYMPOSIUM ON POWER ELECTRONICS, ELECTRICAL DRIVES, AUTOMATION AND MOTION (SPEEDAM) | 2018年
关键词
control algorithm; harmonic disturbances modeling; islanded networks; power quality; smart grid; FILTERS;
D O I
暂无
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The paper proposes a computational procedure able to control in real-time the harmonic disturbance injected by non-linear loads in an islanded MV/LV Smart Grid, characterized by low short circuit power. Aim of the proposed procedure is to keep automatically under acceptable values the penetration of harmonic disturbances caused by different loads, by means of a control algorithm suitable to a Smart Grid context. The control logic has been developed to perform detachments/controls in real-time in function of non-linear loads and their harmonic injection, starting from the assessment of voltage total harmonic distortion (THDV). In order to not exceed the harmonic disturbance thresholds, imposed by the Standard, the smart grid loads are scheduled by means of delayed activations over time, also using energy storage systems. The procedure is able to simulate load variability taking into account power consumption and harmonic profile changes in time. Electrical network, linear and non-linear loads and control algorithm have been implemented in a Simulink model. A case study representing a typical smart grid with residential and tertiary users, electric vehicle charging points and renewable sources is presented.
引用
收藏
页码:650 / 655
页数:6
相关论文
empty
未找到相关数据