Variable-window algorithm for ultra-high-speed distance protection

被引:12
作者
Fazio, G [1 ]
Lauropoli, V
Muzi, F
Sacerdoti, G
机构
[1] Univ Roma Tor Vergata, Dept Elect Engn, Rome, Italy
[2] ACEA SpA, Rome Water & Elect Util, Rome, Italy
[3] Univ Laquila, Dept Elect Engn, Laquila, Italy
[4] Univ Roma La Sapienza, Dept Elect Engn, Rome, Italy
关键词
computer relaying; distance protection; transmission and distribution systems;
D O I
10.1109/TPWRD.2002.807159
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new concept in ultra-high speed distance relay for power line protection. The idea is based on the use of a sampling window shorter than usual to speed commutation. The reduction in protection time is obtained through a variable window that is expanded sample by sample until a satisfactory precision is reached in the calculation of fault quantities. The right window length is obtained automatically via software and time-by-time changes depending on the characteristics of the fault. The algorithm is based on the equation associated to the R-L fault circuit, whose solution is obtained using the phase modified Fourier transform. To validate the proposed procedure, a large number of simulations are performed with reference to an existing 150-kV subtransmission line. In comparison with other solutions, the relay proposed here is very cost-effective and makes it possible to achieve ultra-high speed fault localization not only on high-voltage (HV) networks but also on medium-voltage (MV) distribution networks.
引用
收藏
页码:412 / 419
页数:8
相关论文
共 14 条
  • [1] CLAUS M, 1997, P I ELECT ENG PUBL, V434, P28
  • [2] PERFORMANCE ANALYSIS OF TRANSIENT DETECTORS BASED ON A CLASS OF LINEAR DATA TRANSFORMS
    FRIEDLANDER, B
    PORAT, B
    [J]. IEEE TRANSACTIONS ON INFORMATION THEORY, 1992, 38 (02) : 665 - 673
  • [3] *IEEE, 1997, ADV MICR BAS PROT CO, pCH3
  • [4] JOHNSON DA, 1983, GENE ANAL TECH, V1, P3
  • [5] KENNEDY JM, VARIABLE DIGITAL FIL
  • [6] EXPERIMENTAL EVALUATION OF EMTP-BASED CURRENT TRANSFORMER MODELS FOR PROTECTIVE RELAY TRANSIENT STUDY
    KEZUNOVIC, M
    KOJOVIC, L
    ABUR, A
    FROMEN, CW
    SEVCIK, DR
    PHILLIPS, F
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) : 405 - 412
  • [7] Distance relay application testing using a digital simulator
    Kezunovic, M
    Xia, YQ
    Guo, Y
    Fromen, CW
    Sevcik, DR
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (01) : 72 - 82
  • [8] MATHEWS CA, 1980, P I ELECT ENG PUBL, V185
  • [9] MUZI F, 1999, IEEE POW ENG SOC 199
  • [10] Phadke G., 1988, COMPUTER RELAYING PO