An improved transient stability index for dynamic security assessment using a Marginally Unstable Injection (MUI) approach

被引:0
作者
Cheung, KW [1 ]
机构
[1] ALSTOM ESCA Corp, Bellevue, WA 98004 USA
来源
2000 IEEE POWER ENGINEERING SOCIETY WINTER MEETING - VOLS 1-4, CONFERENCE PROCEEDINGS | 2000年
关键词
transient stability assessment; energy margin; stability index; time-domain simulation;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper is about hybrid methods of combining energy function analysis and conventional time-domain simulation for transient stability assessment. In particular, a new approach called Marginally Unstable Injection (MUI) for developing a more accurate transient stability index is presented. An energy margin for transient stability assessment based on a reduced energy function is formulated. One implementation of the proposed approach is to use a feedback-controlled sequence of short pseudo-faults to impel the stable system to a marginally unstable state. The conceptual differences between MUI and some earlier approaches of hybrid methods are discussed. For illustrative purposes, the technique developed is applied to a 700-bus North America system. Some numerical results are presented.
引用
收藏
页码:931 / 936
页数:4
相关论文
共 7 条
[1]  
CHEUNG KW, 1995, PROCEEDINGS OF THE 1995 AMERICAN CONTROL CONFERENCE, VOLS 1-6, P1545
[2]   A new hybrid method for on-line dynamic security assessment [J].
Cheung, KW .
CONTROL ENGINEERING PRACTICE, 1998, 6 (11) :1373-1380
[3]  
CHIANG HD, 1999, P IEEE PES SUMM M, P287
[4]   BC HYDROS ONLINE TRANSIENT STABILITY ASSESSMENT (TSA) MODEL DEVELOPMENT, ANALYSIS, AND POST-PROCESSING [J].
MANSOUR, Y ;
VAAHEDI, E ;
CHANG, AY ;
CORNS, BR ;
GARRETT, BW ;
DEMAREE, K ;
ATHAY, T ;
CHEUNG, K .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (01) :241-253
[5]   HYBRID TRANSIENT STABILITY ANALYSIS [J].
MARIA, GA ;
TANG, C ;
KIM, J .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1990, 5 (02) :384-393
[6]   TRANSIENT STABILITY INDEX FROM CONVENTIONAL TIME-DOMAIN SIMULATION [J].
TANG, CK ;
GRAHAM, CE ;
ELKADY, M ;
ALDEN, RTH .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) :1524-2530
[7]  
ZHANG Y, 1995, PRINCIPLES PRACTICE, P49