Evaluation of the Reactive Power Support Capability and Associated Technical Costs of Photovoltaic Farms' Operation

被引:10
作者
Lourenco, Luis F. N. [1 ,3 ]
Monaro, Renato M. [1 ]
Salles, Mauricio B. C. [1 ]
Cardoso, Jose R. [1 ]
Queval, Loic [2 ]
机构
[1] Univ Sao Paulo, Escola Politecn, Lab Adv Elect Grids LGRID, BR-05508010 Sao Paulo, Brazil
[2] Sorbonne Univ, Univ Paris Saclay, Univ Paris Sud, CNRS,Cent Supelec,Grp Elect Engn Paris GeePs,UMR, 3 & 11 Rue Joliot Curie, F-91192 Gif Sur Yvette, France
[3] Av Prof Luciano Gualberto 158, BR-05508900 Butanta, SP, Brazil
基金
巴西圣保罗研究基金会;
关键词
solar farm; photovoltaics; reactive power support; STATCOM; technical costs; GENERATION SYSTEMS; VOLTAGE; LOSSES; PERFORMANCE; SIMULATION; TRANSIENTS; CONVERTER; MODELS;
D O I
10.3390/en11061567
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The share of photovoltaic (PV) farms is increasing in the energy mix as power systems move away from conventional carbon-emitting sources. PV farms are equipped with an expensive power converter, which is, most of the time, used well bellow its rated capacity. This has led to proposals to use it to provide reactive power support to the grid. In this framework, this work presents a step-by-step methodology to obtain the reactive power support capability map and the associated technical costs of single- and two-stage PV farms during daytime operation. Results show that the use of two-stage PV farms can expand the reactive power support capability for low irradiance values in comparison to single-stage ones. Besides, despite losses being higher for two-stage PV farms, the technical cost in providing reactive power support is similar for both systems. Based on the obtained maps, it is demonstrated how the profits of a PV farm can be evaluated for the current ancillary services policy in Brazil. The proposed method is of interest to PV farm owners and grid operators to estimate the cost of providing reactive power support and to evaluate the economic feasibility in offering this ancillary service.
引用
收藏
页数:19
相关论文
共 46 条
[1]   Photovoltaic solar system connected to the electric power grid operating as active power generator and reactive power compensator [J].
Albuquerque, Fabio L. ;
Moraes, Adelio J. ;
Guimaraes, Geraldo C. ;
Sanhueza, Sergio M. R. ;
Vaz, Alexandre R. .
SOLAR ENERGY, 2010, 84 (07) :1310-1317
[2]   Pay-as-bid based reactive power market [J].
Amjady, N. ;
Rabiee, A. ;
Shayanfar, H. A. .
ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (02) :376-381
[3]  
[Anonymous], 2010, THESIS
[4]  
[Anonymous], 2005, P INT POW EL C
[5]   Power electronics as efficient interface in dispersed power generation systems [J].
Blaabjerg, F ;
Chen, Z ;
Kjaer, SB .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (05) :1184-1194
[6]  
Blaabjerg F, 1996, IEEE IND APPLIC SOC, P1454, DOI 10.1109/IAS.1996.559258
[7]   POWER LOSSES IN PWM-VSI INVERTER USING NPT OR PT IGBT DEVICES [J].
BLAABJERG, F ;
JAEGER, U ;
MUNKNIELSEN, S ;
PEDERSEN, JK .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1995, 10 (03) :358-367
[8]   Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[9]   A spot pricing mechanism for voltage stability [J].
Chattopadhyay, D ;
Chakrabarti, BB ;
Read, EG .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2003, 25 (09) :725-734
[10]  
de Brito M. A. G., 2011, 2011 International Conference on Clean Electrical Power, P99, DOI 10.1109/ICCEP.2011.6036361