Required limiting impedance and capacity of fault current limiter installed in customer system with synchronous generator

被引:3
作者
Iioka, Daisuke
Yokomizu, Yasunobu
Goto, Masuo
Matsumura, Toshiro
Shimizu, Hirotaka
机构
[1] Nagoya Univ, Dept Elect Engn & Comp Sci, Chikusa Ku, Nagoya, Aichi 4648603, Japan
[2] Nagoya Univ, EcoTopia Sci Inst, Chikusa Ku, Nagoya, Aichi 4648603, Japan
[3] Polytech Univ, Dept Elect Syst Engn, Sagamihara, Kanagawa 2291196, Japan
关键词
distribution network; fault current; voltage control; fault current limiter; distributed generator;
D O I
10.1002/tee.20043
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
We investigated the required limiting impedance and capacity of a fault current limiter (FCL) installed at an incoming feeder of a customer system with a synchronous generator in a utility distribution system. It was assumed that two types of FCL were installed, i.e. a resistive type (R-type) FCL and an inductive type (L-type) FCL. A fault current out of the customer system and a voltage in the customer system were calculated following a three-phase, short-circuit fault occurrence. It was found that the required type of FCL and the required limiting impedance depended on the rated capacity of the generator in order to obtain the suppression of the fault current under 0.1 kA(s), and to maintain of customer voltage between 85 and 100% of the nominal voltage (6.6 kV). The capacity of FCL consisting of the smallest limiting impedance is discussed. (c) 2006 Institute of Electrical Engineers of Japan. Published by John Wiley & Sons, Inc.
引用
收藏
页码:209 / 215
页数:7
相关论文
共 50 条
  • [41] A study on required volume of superconducting element for flux flow resistance type fault current limiter
    Shimizu, H
    Yokomizu, Y
    Goto, M
    Matsumura, T
    Murayama, N
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) : 2052 - 2055
  • [42] Experimental Study on the Current Limiting Characteristics of a Saturated Iron-Core Superconducting Fault Current Limiter in DC Power Systems
    Van Quan Dao
    Lee, JaeIn
    Kim, Chang-Soon
    Park, Minwon
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2021, 31 (05)
  • [43] Short circuit current level reduction in power system by optimal placement of fault current limiter
    Pham Tuan Ngoc
    Singh, Jai Govind
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2017, 27 (12):
  • [44] Power System Stabilization by Fault Current Limiter and Thyristor Controlled Braking Resistor
    Yagami, Masaki
    Tamura, Junji
    2009 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION, VOLS 1-6, 2009, : 952 - +
  • [45] Influence of fault current limiter on axial torsion torque of distributed power system
    Yang, YB
    Ota, Y
    Ukai, H
    Nakamura, K
    POWERCON 2002: INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS 1-4, PROCEEDINGS, 2002, : 163 - 168
  • [46] Experimental study on superconducting fault current limiting transformer for fault current suppression and system stability improvement
    Kagawa, H
    Hayakawa, N
    Kashima, N
    Nagaya, S
    Okubo, H
    PHYSICA C-SUPERCONDUCTIVITY AND ITS APPLICATIONS, 2002, 372 (PART 3): : 1706 - 1710
  • [47] Fault Current Limitation Coordination in Power Transmission System With Superconducting Fault Current Limiting Cables (SFCLC)
    Kojima, Hiroki
    Osawa, Takeshi
    Hayakawa, Naoki
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2015, 25 (03)
  • [49] A Novel Topology of DC Distribution Network with Fault Current Limiting Static Synchronous Series Compensator
    Wu, Zhenliang
    Jiang, Daozhuo
    Lao, Dejia
    Ying, Qunmin
    Du, Yi
    2017 IEEE PES INNOVATIVE SMART GRID TECHNOLOGIES CONFERENCE EUROPE (ISGT-EUROPE), 2017,
  • [50] Comprehensive coordination of radial distribution network protection in the presence of synchronous distributed generation using fault current limiter
    Chabanloo, Reza Mohammadi
    Maleki, Mandi Ghotbi
    Agah, S. Mohammad Mousavi
    Habashi, Ehsan Mokhtarpour
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2018, 99 : 214 - 224