Energy Evaluation of Multiple Stage Commercial Refrigeration Architectures Adapted to F-Gas Regulation

被引:30
作者
Catalan-Gil, Jesus [1 ]
Sanchez, Daniel [1 ]
Llopis, Rodrigo [1 ]
Nebot-Andres, Laura [1 ]
Cabello, Ramon [1 ]
机构
[1] Jaume I Univ, Dept Mech Engn & Construct, Campus Riu Sec, E-12071 Castellon de La Plana, Spain
关键词
R744 transcritical booster; subcritical booster; cascade; parallel compression; ejector; commercial/retail refrigeration; INTERNAL HEAT-EXCHANGER; SUPERMARKET REFRIGERATION; THEORETICAL EVALUATION; CO2; SYSTEM; PERFORMANCE; CYCLE; OPTIMIZATION; COOLER/CONDENSER; CONFIGURATIONS;
D O I
10.3390/en11071915
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This work analyses different refrigeration architectures for commercial refrigeration providing service to medium and low temperature simultaneously: HFC/R744 cascade, R744 transcritical booster, R744 transcritical booster with parallel compression, R744 transcritical booster with gas ejectors, R513A cascade/R744 subcritical booster, and R513A cascade/R744 subcritical booster with parallel compression. The models were developed using compressor manufacturers' data and real restrictions of each system component. Limitations and operating range of each component and architecture were analysed for environment temperatures from 0 to 40 degrees C considering thermal loads and environment temperature profiles for warm climates. For booster systems, cascade with subcritical booster with parallel compression provide highest coefficient of performance (COP) for temperatures below 12 degrees C and above 30 degrees C with COP increases compared basic booster up to 60.6%, whereas for transcritical boosters, architecture with gas ejectors obtains the highest COP with COP increases compared to the basic booster up to 29.5%. In annual energy terms, differences among improved booster systems are below 8% in the locations analysed. In Total Equivalent Warming Impact (TEWI) terms, booster architectures get the lowest values with small differences between improved boosters.
引用
收藏
页数:31
相关论文
共 65 条
[1]  
AIRAH, 2012, Methods of calculating total equivalent warming impact (TEWI) 2012
[2]  
[Anonymous], CLIMATE CHANGE 2007
[3]  
[Anonymous], 2016, F GAS REG SHAK HVAC
[4]  
[Anonymous], P 7 IIR AMM CO2 REFR
[5]  
[Anonymous], P 12 IIR G LOR NAT W
[6]   Development and performance mapping of a multi-ejector expansion work recovery pack for R744 vapour compression units [J].
Banasiak, Krzysztof ;
Hafner, Armin ;
Kriezi, Ekaterini E. ;
Madsen, Kenneth B. ;
Birkelund, Michael ;
Fredslund, Kristian ;
Olsson, Rickard .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 57 :265-276
[7]  
Bitzer, 2017, Bitzer CO2 Booster Rack
[8]  
Boudreau P.J., 2013, COMPRESSOR OPERATING
[9]  
British Refrigeration Association Action Group, 2015, PUTT US REPL REFR
[10]   Experimental analysis of R744 parallel compression cycle [J].
Chesi, Andrea ;
Esposito, Fabio ;
Ferrara, Giovanni ;
Ferrari, Lorenzo .
APPLIED ENERGY, 2014, 135 :274-285