Pollution Flashover Under Different Contamination Profiles on High Voltage Insulator: Numerical and Experiment Investigation

被引:40
作者
Salem, Ali Ahmed [1 ]
Abd-Rahman, R. [1 ]
Rahiman, Wan [2 ]
Al-Gailani, Samir Ahmed [2 ]
Al-Ameri, Salem Mgammal [1 ]
Ishak, Mohd Taufiq [3 ]
Sheikh, Usman Ullah [4 ]
机构
[1] Univ Tun Hussein Onn Malaysia, Fac Elect & Elect Engn, Johor Baharu 86400, Malaysia
[2] Univ Sains Malaysia, Sch Elect & Elect Engn, George Town 14300, Malaysia
[3] Natl Def Univ Malaysia UPNM, Fac Engn, Kuala Lumpur 57000, Malaysia
[4] Univ Teknol Malaysia, Fac Engn, Sch Elect Engn, Johor Baharu 81310, Malaysia
关键词
Insulators; Finite element analysis; Pollution; Flashover; Electric potential; Mathematical model; Glass; Polluted insulators; contamination profiles; flashover voltage gradient; numerical model; finite element method (FEM); power dissipation; POLYMERIC INSULATOR; AC;
D O I
10.1109/ACCESS.2021.3063201
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This work aimed to study the influence of contamination profiles and humidity on flashover electrical characteristics of polluted insulators. Firstly, the flashover tests on cap and pin glass insulators under four pollution levels represented by salinity were conducted. Eight artificial contamination profiles based on the solid layer method have been modeled for the selected insulators. The numerical analysis has been used to determine the insulator electrical characteristics such as potential, electric field, and power dissipation under proposed contamination profiles using finite element methods (FEM). Next, the power dissipation has been simulated with consideration of thermal stress propagation in locations with high power. Finally, flashover voltage gradient tests have been conducted under various humidity and contamination profiles. The values of the flashover voltage gradient due to pollution were determined as the percentage of the value of the flashover voltage gradient in the clean condition which was identified as the reference point. The numerical model indicated that the initiation of arc generally occurs at area in which the electric field and power dissipation is maximum. It was also observed from experimental results that the flashover voltage gradient under different contamination profiles has different values depends on the location and dimension of the pollution region.
引用
收藏
页码:37800 / 37812
页数:13
相关论文
共 32 条
[1]  
Abd-Rahman R., 2016, 2016 IEEE International Conference on Power and Energy (PECon), P610, DOI 10.1109/PECON.2016.7951633
[2]   Leakage current analysis of polymeric insulators under uniform and non-uniform pollution conditions [J].
Ahmadi-Joneidi, Iman ;
Shayegani-Akmal, Amir Abbas ;
Mohseni, Hossein .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (11) :2947-2957
[3]  
Al-Ameri, 2019, INT J POWER ELECT DR, DOI [10.11591/ijpeds.v10.i2.pp602-610, DOI 10.11591/IJPEDS.V10.I2.PP602-610]
[4]   Electrical Field Computation of Polymeric Insulator using Reduced Dimension Modeling [J].
Anbarasan, R. ;
Usa, S. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (02) :739-746
[5]  
[Anonymous], 2013, ARTICIAL POLLUTION T
[6]  
Asadpoor M., 2012, INT J APPL SCI ENG R, V1, P165, DOI [10.6088/ijase.0020101017, DOI 10.6088/IJASE.0020101017]
[7]   Improvement of Electric Field Distribution by Integrating Composite Insulators in a 400 kV AC Double Circuit Line in Algeria [J].
Bouhaouche, M. ;
Mekhaldi, A. ;
Teguar, M. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (06) :3549-3558
[8]   AC Flashover Voltage Model for Polluted Suspension Insulators and an Experimental Investigation in Salt Fog [J].
Dong, Bingbing ;
Zhang, Zhu ;
Xiang, Nianwen ;
Yang, Hejun ;
Xu, Shuiqing ;
Cheng, Tingli .
IEEE ACCESS, 2020, 8 :187411-187418
[9]   Risk assessment of desert pollution on composite high voltage insulators [J].
El-Shahat, Mohammed ;
Anis, Hussein .
JOURNAL OF ADVANCED RESEARCH, 2014, 5 (05) :569-576
[10]  
Hampton B.F., 1964, PROC, V111, P985