Chilled ceiling and displacement ventilation system for energy savings: A case study

被引:28
|
作者
Ghali, K.
Ghaddar, N.
Ayoub, M.
机构
[1] Amer Univ Beirut, Fac Engn & Architecture, Dept Mech Engn, Beirut 1107 2020, Lebanon
[2] Beirut Arab Univ, Dept Mech Engn, Beirut, Lebanon
关键词
displacement ventilation; chilled ceiling; stratification height; vertical temperature gradient;
D O I
10.1002/er.1266
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper studies the design and performance of cooled ceiling and displacement ventilation (CC/DV) systems application for buildings in Beirut for the purpose of saving energy. The transient thermal response of spaces cooled by the combined CC/DV system is needed for performance assessment. For that reason, the plume-multi-layer model of CC/DV cooled spaces is extended to transient applications. A design procedure for the combined CC/DV system in Beirut humid climate and buildings is developed to insure that both indoor air quality and comfort are satisfied within the conditioned zone. The contribution of the proposed procedure is that it guarantees that the stratification height (occupied zone) is at 1.1 m taking into consideration the plumes from internal sources and non-isothermal walls. The design procedure is applied to a case study in Beirut to design a system for a typical office space at 85 W m(-2) sensible cooling load. The CC/DV system size is compared with the size of a conventional mixed convection system. It is found that the size of the CC/DV system is 10.2 kW compared to conventional system size of 7.9 and 13.4 kW at the 30 and 100% fresh air supply, respectively. For the same indoor air quality and thermal comfort level, the CC/DV system consumed 21% less cooling energy than the conventional 100% fresh air system over the cooling season. The initial cost of the CC/DV system is higher, but the pay back period based on transient operation is less than 5 yr. Copyright (c) 2006 John Wiley & Sons, Ltd.
引用
收藏
页码:743 / 759
页数:17
相关论文
共 50 条
  • [1] Chilled ceiling and displacement ventilation system: Laboratory study with high cooling load
    Schiavon, Stefano
    Bauman, Fred S.
    Tully, Brad
    Rimmer, Julian
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2015, 21 (07) : 944 - 956
  • [2] A combined system of chilled ceiling, displacement ventilation and desiccant dehumidification
    Hao, Xiaoli
    Zhang, Guoqiang
    Chen, Youming
    Zou, Shenghua
    Moschandreas, Demetrios. J.
    BUILDING AND ENVIRONMENT, 2007, 42 (09) : 3298 - 3308
  • [3] Design Charts for Combined Chilled Ceiling Displacement Ventilation System
    Ghaddar, Nesreen
    Ghali, Kamel
    Saadeh, Ralph
    Keblawi, Amer
    ASHRAE TRANSACTIONS 2008, VOL 114, PT 2, 2008, 114 : 574 - +
  • [4] Energy Saving Using Mixed Air in Rooms Conditioned by Chilled Ceiling Displacement Ventilation System
    Chakroun, W.
    Ghali, K.
    Ghaddar, N.
    ASHRAE TRANSACTIONS 2011, VOL 117, PT 2, 2011, 117 : 67 - 75
  • [5] Optimized selection and operation of the combined chilled ceiling system and displacement ventilation
    Ghaddar, N.
    Ghali, K.
    Saadeh, R.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2010, 34 (15) : 1328 - 1340
  • [6] Comparison of chilled ceiling and mixing ventilation assisted by intermittent personalized ventilation: Thermal comfort and energy savings
    Al Assaad D.
    Ghali K.
    Ghaddar N.
    Renewable Energy and Power Quality Journal, 2020, 18 : 431 - 436
  • [7] An Energy Efficient Air Conditioning System using Displacement Ventilation and Chilled Ceiling for Modern Office Buildings
    Parameshwaran, R.
    Karunakaran, R.
    Muthumariappan, S.
    Bipasha, S.
    INTERNATIONAL JOURNAL OF VENTILATION, 2010, 9 (01) : 25 - 44
  • [8] Air quality in rooms conditioned by chilled ceiling and mixed displacement ventilation for energy saving
    Chakroun, W.
    Ghali, K.
    Ghaddar, N.
    ENERGY AND BUILDINGS, 2011, 43 (10) : 2684 - 2695
  • [9] NUMERICAL STUDY ON THERMAL INDOOR ENVIRONMENT OF AN OFFICE WITH HYBRID SYSTEM OF CHILLED CEILING PANEL AND DISPLACEMENT VENTILATION
    Zhao, Lei
    Feng, Yannan
    Yuan, Feng
    Zhang, Peidong
    ACRA 2009: PROCEEDINGS OF THE 4TH ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING, 2009, : 547 - 552
  • [10] Chilled ceiling and displacement ventilation aided with personalized evaporative cooler
    Chakroun, W.
    Ghaddar, N.
    Ghali, K.
    ENERGY AND BUILDINGS, 2011, 43 (11) : 3250 - 3257