Investigation of Spatial Control Strategies for AHWR: A Comparative Study

被引:6
作者
Munje, R. K. [1 ]
Patre, B. M. [2 ]
Londhe, P. S. [2 ]
Tiwari, A. P. [3 ,4 ]
Shimjith, S. R. [3 ]
机构
[1] KK Wagh Inst Engn Educ & Res, Nasik 422003, India
[2] SGGS Inst Engn & Technol, Nanded 431606, India
[3] Bhabha Atom Res Ctr, Reactor Control Syst Design Sect, Bombay 400085, Maharashtra, India
[4] Homi Bhabha Natl Inst, Bombay 400094, Maharashtra, India
关键词
Advanced heavy water reactor; fuzzy logic control; output feedback; sliding mode control; HEAVY-WATER REACTOR; PERIODIC OUTPUT-FEEDBACK; SINGULAR PERTURBATIONS; NUCLEAR-REACTOR; LARGE PHWR; DESIGN; OSCILLATIONS; DECOMPOSITION; STABILIZATION; REDUCTION;
D O I
10.1109/TNS.2016.2519606
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Large nuclear reactors such as the Advanced Heavy Water Reactor (AHWR), are susceptible to xenon-induced spatial oscillations in which, though the core average power remains constant, the power distribution may be nonuniform as well as it might experience unstable oscillations. Such oscillations influence the operation and control philosophy and could also drive safety issues. Therefore, large nuclear reactors are equipped with spatial controllers which maintain the core power distribution close to desired distribution during all the facets of operation and following disturbances. In this paper, the case of AHWR has been considered, for which a number of different types of spatial controllers have been designed during the last decade. Some of these designs are based on output feedback while the others are based on state feedback. Also, both the conventional and modern control concepts, such as linear quadratic regulator theory, sliding mode control, multirate output feedback control and fuzzy control have been investigated. The designs of these different controllers for the AHWR have been carried out using a 90th order model, which is highly stiff. Hence, direct application of design methods suffers with numerical ill-conditioning. Singular perturbation and time-scale methods have been applied whereby the design problem for the original higher order system is decoupled into two or three subproblems, each of which is solved separately. Nonlinear simulations have been carried out to obtain the transient responses of the system with different types of controllers and their performances have been compared.
引用
收藏
页码:1236 / 1246
页数:11
相关论文
共 51 条
[1]   Drum-boiler dynamics [J].
Åström, KJ ;
Bell, RD .
AUTOMATICA, 2000, 36 (03) :363-378
[2]  
Bernard J. A., 1985, Proceedings of the 1985 American Control Conference (Cat. No. 85CH2119-6), P1466
[3]   POLE ASSIGNMENT BY PIECEWISE CONSTANT OUTPUT-FEEDBACK [J].
CHAMMAS, AB ;
LEONDES, CT .
INTERNATIONAL JOURNAL OF CONTROL, 1979, 29 (01) :31-38
[4]   Design and stability analysis of single-input fuzzy logic controller [J].
Choi, BJ ;
Kwak, SW ;
Kim, BK .
IEEE TRANSACTIONS ON SYSTEMS MAN AND CYBERNETICS PART B-CYBERNETICS, 2000, 30 (02) :303-309
[5]   DECOMPOSITION OF NEAR-OPTIMUM REGULATORS FOR SYSTEMS WITH SLOW AND FAST MODES [J].
CHOW, JH ;
KOKOTOVIC, PV .
IEEE TRANSACTIONS ON AUTOMATIC CONTROL, 1976, 21 (05) :701-705
[6]  
Da Ruan, 1999, FUZZ-IEEE'99. 1999 IEEE International Fuzzy Systems. Conference Proceedings (Cat. No.99CH36315), P1712, DOI 10.1109/FUZZY.1999.790164
[7]   Fractional Order Modeling of a PHWR Under Step-Back Condition and Control of Its Global Power With a Robust PIλDμ Controller [J].
Das, Saptarshi ;
Das, Shantanu ;
Gupta, Amitava .
IEEE TRANSACTIONS ON NUCLEAR SCIENCE, 2011, 58 (05) :2431-2441
[8]   Networked Control of a Large Pressurized Heavy Water Reactor (PHWR) With Discrete Proportional-Integral-Derivative (PID) Controllers [J].
Dasgupta, Soumya ;
Routh, Avijit ;
Banerjee, Shohan ;
Agilageswari, K. ;
Balasubramanian, R. ;
Bhandarkar, S. G. ;
Chattopadhyay, Sujit ;
Kumar, Manoj ;
Gupta, Amitava .
IEEE TRANSACTIONS ON NUCLEAR SCIENCE, 2013, 60 (05) :3879-3888
[9]  
Duderstadt J.J., 1991, Nuclear Reactor Analysis
[10]  
Emara HM, 2002, P AMER CONTR CONF, V1-6, P5066, DOI 10.1109/ACC.2002.1025469