Risk Analysis of Lightning and Surge Protection Devices for Power Energy Structures

被引:6
作者
Liu, Chien-Hsun [1 ]
Muna, Yirga Belay [1 ]
Chen, Yu-Tung [1 ]
Kuo, Cheng-Chien [1 ]
Chang, Hung-Yi [1 ]
机构
[1] Natl Taiwan Univ Sci & Technol, Dept Elect Engn, 43,Sec 4,Keelung Rd, Taipei 106, Taiwan
关键词
lightning risk; protection measures; surge protective device;
D O I
10.3390/en11081999
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper studies the risk data and protection measurements of lightning based on the IEC62305 standard. In addition, Visual Basic (VB) is used to build a lightning risk calculation program with a Graphical User Interface (GUI). The data structure, including environment data, line data, zone data, economic data, and protection measures is designed to simulate risk of loss of human life (R1) and risk of loss of economic value (R4). To achieve the most economical protection structure design, additional protection measurements and annual savings are considered. In the practical application, the main purpose is to discuss effective protection distances of surge protective devices (SPDs) for low-voltage power distribution. This paper takes advantage of Electromagnetic Transients Program (EMTP) to simulate the voltage of equipment with different types of loads and length of the cable. After using the protection measures, the value of risk of human life reduces form 21.299 x 10(-5) to 0.439 x 10(-5) and the value of risk of economic value reduces from 2696.754 x 10(-5) to 98.062 x 10(-5). The results mean that the protection measures let the values of the risk below the tolerance. By considering the annual cost saving. Assume the cost of protection measures, the interest rate, the depreciation rate, and the maintenance rate are 150,000 $, 4%, 5%, and 1%, respectively. The annual cost before using protective measures, the annual cost after using protective measures, the annual cost of protective measures, and the annual cost saving are $925,000, $33,635, $15,000 and $876,365, respectively. Consequently, it is feasible that the simulation result can provide users with great suggestions to choose the best installation location and achieve the most effective protection design.
引用
收藏
页数:16
相关论文
共 17 条
[11]   Lightning performance analysis of overhead transmission lines using the EMTP [J].
Martinez, JA ;
Castro-Aranda, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) :2200-2210
[12]  
Mounir M. M., 2013, P 2013 INT C COMP EL
[13]   Failure risk prediction using artificial neural networks for lightning surge protection of underground MV cables [J].
Orille-Fernandez, Angel L. ;
Khalil, Nabil ;
Rodriguez, Santiago Bogarra .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1278-1282
[14]   Statistical evaluation of lightning-related failures for the optimal location of surge arresters on the power networks [J].
Shariatinasab, R. ;
Vahidi, B. ;
Hosseinian, S. H. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2009, 3 (02) :129-144
[15]   Development of an adaptive neural-fuzzy inference system based meta-model for estimating lightning related failures in polluted environments [J].
Shariatinasab, Reza ;
Safar, Jalil Ghayur ;
Mobarakeh, Mohsen Akafi .
IET SCIENCE MEASUREMENT & TECHNOLOGY, 2014, 8 (04) :187-195
[16]  
Stefanescu S, 2016, INT CONF EXPO ELECTR, P504, DOI 10.1109/ICEPE.2016.7781391
[17]  
Trainba Mahmud, 2017, WSEAS Transactions on Power Systems, V12, P107