The Mechanism and Diagnosis of Insulation Deterioration Caused by Moisture Ingress into Oil-Impregnated Paper Bushing

被引:19
作者
Qi, Bo [1 ]
Dai, Quanmin [1 ]
Li, Chengrong [1 ]
Zeng, Zipeng [1 ]
Fu, Mingli [2 ]
Zhuo, Ran [2 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[2] Elect Power Res Inst China Southern Power Grid, Guangzhou 510530, Guangdong, Peoples R China
基金
国家重点研发计划; 中国国家自然科学基金;
关键词
bushing; moisture ingress; insulation deterioration; fault diagnosis; HIGH-VOLTAGE BUSHINGS; DIELECTRIC RESPONSE;
D O I
10.3390/en11061496
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The healthy state of insulation in oil-impregnated bushings is traditionally evaluated by tan and capacitance at power frequency and mostly at 10 kV in the test standard. However, there has frequently been insulation accidents induced by moisture ingress (MI) for bushings that have passed the standard. The mechanism and new diagnostic features for MI into bushings were not distinct enough and an accurate test method is urgently needed research. To address this technical gap, a bushing model with a transparent sheath was designed and an ultrasonic humidifier device was adopted to simulate the environment of MI in bushings and recorded by digital camera. The parameters of dielectric dissipation factor, capacitance, partial discharge (PD), frequency domain response, and moisture content in oil were measured at room temperature with time. The results presented that both the increment dissipation factor at low frequency of 0.001 Hz and the increment dissipation factor of 1.2 U-m could be used for detecting the earlier insulation defect of oil-impregnated paper (OIP) bushings. The phase resolved partial discharge (PRPD) can serve as the diagnostic basis of the severe state (S-3) of insulation deterioration caused by MI into bushings around the phases of 0-117 degrees, 151-303 degrees, and 325-360 degrees. The research findings would provide a useful reference for the condition diagnosis and maintenance of OIP bushings. Especially, the increment detection of Frequency Domain Spectroscopy (FDS) at the frequency of 1 mHz and 10 kHz was recommended firstly for the operative bushings in real sites.
引用
收藏
页数:12
相关论文
共 16 条
[1]   Field experiences with measurements of dielectric response in frequency domain for power transformer diagnostics [J].
Blennow, J ;
Ekanayake, C ;
Walczak, K ;
García, B ;
Gubanski, SM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) :681-688
[2]  
Braun J. M., 2000, Conference Record of the 2000 IEEE International Symposium on Electrical Insulation (Cat. No.00CH37075), P469, DOI 10.1109/ELINSL.2000.845550
[3]  
Dai QM, 2016, C ELECT INSUL DIEL P, P319, DOI 10.1109/CEIDP.2016.7785641
[4]   Apparatus for Online Power Transformer Winding Monitoring Using Bushing Tap Injection [J].
De Rybel, Tom ;
Singh, Arvind ;
Vandermaar, John A. ;
Wang, May ;
Marti, Jose R. ;
Srivastava, K. D. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2009, 24 (03) :996-1003
[5]   Dielectric response methods for diagnostics of power transformers [J].
Gubanski, SM ;
Boss, P ;
Csépes, G ;
Houhanessian, VD ;
Filippini, J ;
Guuinic, P ;
Gäfvert, U ;
Karius, V ;
Lapworth, J ;
Urbani, G ;
Werelius, P ;
Zaengl, W .
IEEE ELECTRICAL INSULATION MAGAZINE, 2003, 19 (03) :12-18
[6]  
Kruger M., 2010, TECH REP 25A28
[7]   On-line diagnostics of high-voltage bushings and current transformers using the sum current method [J].
Lachman, MF ;
Walter, W ;
von Guggenberg, PA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) :155-162
[8]  
Lokhanin A.K., 2002, INTERNAL INSULATION
[9]   Deriving an equivalent circuit of transformers insulation for understanding the dielectric response measurements [J].
Saha, TK ;
Purkait, P ;
Müller, F .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) :149-157
[10]   Dielectric spectroscopic measurements on transformer oil-paper insulation under controlled laboratory conditions [J].
Setayeshmehr, A. ;
Fofana, I. ;
Eichler, C. ;
Akbari, A. ;
Borsi, H. ;
Gockenbach, E. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (04) :1100-1111