Flow condensation heat transfer and pressure drop of R134a alternative refrigerants R513A and R450A in 0.95-mm diameter minichannels

被引:18
作者
Morrow, Jordan A. [1 ]
Derby, Melanie M. [1 ]
机构
[1] Kansas State Univ, Alan Levin Dept Mech & Nucl Engn, Rathbone Hall,1701B Platt St, Manhattan, KS 66506 USA
基金
美国国家科学基金会;
关键词
Condensation; Low global warming potential; Low GWP; Alternative refrigerant; Two-phase flow; TRANSFER COEFFICIENT; MINI-CHANNEL; PERFORMANCE; R1234ZE(E); OLEFINS;
D O I
10.1016/j.ijheatmasstransfer.2022.122894
中图分类号
O414.1 [热力学];
学科分类号
摘要
Due to the Kigali amendment to the Montreal Protocol, refrigerants such as R134a are targeted for phasedown or phaseout due to their global warming potential (GWP) and lower GWP refrigerants are being considered to replace R134a. Since the condenser is typically responsible for 50% of the charge of a refrigeration system, it is vital to have a fundamental understanding of the flow condensation heat transfer performance of low GWP refrigerants such as R513A and R450A. Experimental flow condensation heat transfer coefficient data are reported for R134a, R513A, and R450A in seven parallel 0.95 mm diameter mini-channels for a range of mass fluxes (i.e., 200 - 500 kg/m(2) s) and qualities (i.e., 0.2 - 0.8) at a saturation temperature of 40 degrees C. The heat transfer coefficient uncertainties for all experiments were +/- 6.3 21.2%, with an average of +/- 9.8%. Condensation heat transfer coefficients for R134a, R513A, and R450A all increased with increasing mass flux and quality. R513A condensation heat transfer coefficients were 2.6 25.6% lower than R134a heat transfer coefficients and pressure drops were 4.5 - 14.0% lower than R134a pressure drops. R450A heat transfer coefficients were 2.4% higher than R134a at higher mass fluxes and qualities and up to 11.7% lower than R134a at lower mass fluxes than R134a heat transfer coefficients; R450A pressure drop were comparable to R134a pressure drop (i.e., 5.0% higher to 9.5% lower). The data were compared to three condensation correlations - Shah (2016), Kim and Mudawar (2013), and Cavallini et al. (2011); the data were predicted with mean average errors of 23.4%, 15.9%, and 23.4%, respectively. (c) 2022 Elsevier Ltd. All rights reserved.
引用
收藏
页数:10
相关论文
共 45 条
  • [1] Measurement and modeling of condensation heat transfer in non-circular microchannels
    Agarwal, Akhil
    Bandhauer, Todd M.
    Garimella, Srinivas
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (06): : 1169 - 1179
  • [2] Condensation of ternary low GWP zeotropic mixtures inside channels
    Azzolin, Marco
    Berto, Arianna
    Bortolin, Stefano
    Moro, Lorenzo
    Del Col, Davide
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 103 : 77 - 90
  • [3] Ozone depletion and global warming: Case for the use of natural refrigerant - a review
    Bolaji, B. O.
    Huan, Z.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 18 : 49 - 54
  • [4] Thermophysical properties and heat transfer and pressure drop performance potentials of hydrofluoro-olefins, hydrochlorofluoro-olefins, and their blends
    Brown, J. Steven
    Zilio, Claudio
    Brignoli, Riccardo
    Cavallini, Alberto
    [J]. HVAC&R RESEARCH, 2014, 20 (02): : 203 - 220
  • [5] The next generation of refrigerants - Historical review, considerations, and outlook
    Calm, James M.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2008, 31 (07) : 1123 - 1133
  • [6] Heat transfer and pressure drop of natural refrigerants in minichannels (low charge equipment)
    Cavallini, Alberto
    Del Col, Davide
    Rossetto, Luisa
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (02): : 287 - 300
  • [7] Condensation Heat Transfer and Pressure Losses of High- and Low-Pressure Refrigerants Flowing in a Single Circular Minichannel
    Cavallini, Alberto
    Bortolin, Stefano
    Del Col, Davide
    Matkovic, Marko
    Rossetto, Luisa
    [J]. HEAT TRANSFER ENGINEERING, 2011, 32 (02) : 90 - 98
  • [8] Colombo L.P.M., 2019, ANALISI SPERIMENTALE
  • [9] Derby M.M., 2013, Study of flow condensation enhancement with hydrophobic and hydrophilic patterns
  • [10] Condensation heat transfer in square, triangular, and semi-circular mini-channels
    Derby, Melanie
    Lee, Hee Joon
    Peles, Yoav
    Jensen, Michael K.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2012, 55 (1-3) : 187 - 197