Experimental study on the flame extension and risk analysis of a diffusion impinging flame in confined compartment

被引:5
|
作者
Wang, Aijuan [1 ]
Manescau, Brady [1 ]
Chetehouna, Khaled [1 ]
Rudz, Steve [2 ]
Lamoot, Ludovic [1 ]
机构
[1] Univ Orleans, INSA Ctr Val Loire, PRISME, EA 4229, 88 Blvd Lahitolle, F-18000 Bourges, France
[2] Univ Orleans, CNRS, UMR 7344, GREMI, Bourges, France
关键词
Impinging flame; flame extension; confined compartment; equivalence ratio; auto-ignition; CEILING JETS; FIRE DETECTION; LENGTHS; WALL; GAS;
D O I
10.1177/07349041211015766
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this work, an experimental investigation on a diffusion impinging flame in a confined compartment was performed. The objective was to study the influence of confinement on the behavior of a flame impinging the ceiling and to deduce the auto-ignition risk of the smoke produced in the confined compartment. For this, configurations with five confinement levels were constructed by the condition of windows and/or door in the compartment and the variation of the heat release rates was made between 0.5 and 18.6 kW. To evaluate the flame morphology and flame extension length, an image processing method based on the direct linear transformation algorithm and the fire segmentation algorithm was adopted. From the experimental data, it was shown that the heat release rate of 4.6 kW presents a critical value for the flame extension in confined configurations, which corresponds to the equivalence ratio of the enclosure greater than 1, highlighting an under-ventilated environment. In addition, an auto-ignition risk analysis of smoke with unburnt gas in the compartment was carried out. The concentration and temperature of these gases were compared to the lower flammability limits and the auto-ignition temperature. It was observed that there was auto-ignition risk of the smoke under the ceiling, especially in the confined compartment of equivalence ratio greater than 1. Under these conditions, it is possible to have a fire spread to another compartment.
引用
收藏
页码:285 / 308
页数:24
相关论文
共 50 条
  • [1] Experimental Study on Flame Extension and Pattern Analysis of Jet Fire Impinging Wood Plates
    Xinxing Chen
    Xiaoyang Yu
    Yunru Lin
    Guangying Li
    Jiyun Wang
    Ruowen Zong
    Fire Technology, 2023, 59 : 359 - 380
  • [2] Experimental Study on Flame Extension and Pattern Analysis of Jet Fire Impinging Wood Plates
    Chen, Xinxing
    Yu, Xiaoyang
    Lin, Yunru
    Li, Guangying
    Wang, Jiyun
    Zong, Ruowen
    FIRE TECHNOLOGY, 2023, 59 (02) : 359 - 380
  • [3] Experimental investigation of the confinement effect on a flame impinging a ceiling in an enclosure
    Wang, A. J.
    Manescau, B.
    Chetehouna, K.
    De Izarra, C.
    Rudz, S.
    FIRE SAFETY JOURNAL, 2021, 122
  • [4] Structure of Combustion Enhancement on Impinging Diffusion Flame
    Leu, Jai-Houng
    Su, Ay
    MECHANICAL ENGINEERING AND MATERIALS, PTS 1-3, 2012, 152-154 : 872 - +
  • [5] Heat transfer characteristics of an impinging inverse diffusion flame
    Sze, LK
    Cheung, CS
    Leung, CW
    COMBUSTION SCIENCE AND TECHNOLOGY IN ASIA-PACIFIC AREA: TODAY AND TOMORROW, 2003, : 99 - 103
  • [6] Analysis of the quenching behavior in impinging flame: Flow and thermal characteristics
    He, Canxing
    Sun, Meng
    Jiang, Jieyu
    Yu, Yongzhe
    Liu, Kun
    Zhang, Bin
    NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2024, 85 (12) : 1973 - 1987
  • [7] Experimental study of flame extension lengths and fire pattern lengths induced by the turbulent jet fire impinging on inclined wooden boards
    Lin, Yunru
    Yu, Xiaoyang
    Chen, Xinxing
    Li, Guangying
    Yu, Xiao
    Zong, Ruowen
    THERMAL SCIENCE AND ENGINEERING PROGRESS, 2024, 49
  • [8] Experimental study of impinging flame structures and thermal characteristics in ceiling flow generated by fuel jet diffusion combustion with air entrainment constraint in a corner
    Fang, Xu
    Sun, Xiepeng
    Zhang, Xiaolei
    Yuen, Richard K. K.
    Hu, Longhua
    FUEL, 2022, 323
  • [9] Characterization of impingement region from an impinging inverse diffusion flame jet
    Dong, L. L.
    Cheung, C. S.
    Leung, C. W.
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2013, 56 (1-2) : 360 - 369
  • [10] Experimental study of flame geometry of flame spread in a moving body under forced flow in a long and narrow confined space
    Liu, Shizhe
    An, Weibin
    Guang, Daqing
    Wang, Zhe
    An, Weiguang
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2024, 235