Experimental Study of a Gas Engine-driven Heat Pump System for Space Heating and Cooling

被引:16
作者
Zhang, Wei [1 ]
Yang, Xianzhao [1 ]
Wang, Tao [1 ]
Peng, Xueyuan [1 ]
Wang, Xiaolin [2 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Xian 710049, Shaanxi, Peoples R China
[2] Univ Tasmania, Sch Engn, Hobart, Tas 7001, Australia
来源
CIVIL ENGINEERING JOURNAL-TEHRAN | 2019年 / 5卷 / 10期
关键词
Gas Engine-Driven Heat Pump; Pace Cooling; Space Heating; PER; Heat Recovery; PERFORMANCE; ENERGY;
D O I
10.28991/cej-2019-03091411
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this paper, the performance of a gas engine-driven heat pump (GEHP) was experimentally studied for space heating and cooling. An experimental test facility was developed for this purpose. The effect of key parameters on system performance was investigated under both cooling and heating modes. The results showed that as the engine speed increased from 1400 to 2000 rpm, the cooling and heating capacities increased by 23% and 28.5%, respectively while the GEHP system Primary Energy Ratio (PER) decreased by 13.5% and 11.7% in the cooling and heating modes, respectively. The system PER in the cooling mode was found lower than that in the heating mode. This indicated that heat recovery from the engine cylinder and exhaust gas was very important for improving the GEHP system performance. In the heating mode, the ambient temperature and condenser water flow rate had a large effect on the system heating capacity and PER, and insignificant effect on the gas energy input. In the cooling mode, the chilled water inlet temperature showed a large effect on both cooling capacity and gas energy input while the chilled water flow rate had a large effect on cooling capacity and insignificant effect on the gas energy input.
引用
收藏
页码:2282 / 2295
页数:14
相关论文
共 17 条
[1]  
Bevington Philip R., 1993, COMPUT PHYS, V7, P415, DOI DOI 10.1063/1.4823194
[2]   Comparison of natural gas driven heat pumps and electrically driven heat pumps with conventional systems for building heating purposes [J].
Brenn, J. ;
Soltic, P. ;
Bach, Ch. .
ENERGY AND BUILDINGS, 2010, 42 (06) :904-908
[3]   Performance of a gas engine driven heat pump for hot water supply systems [J].
Elgendy, E. ;
Schmidt, J. ;
Khalil, A. ;
Fatouh, M. .
ENERGY, 2011, 36 (05) :2883-2889
[4]   Experimental study of gas engine driven air to water heat pump in cooling mode [J].
Elgendy, E. ;
Schmidt, J. .
ENERGY, 2010, 35 (06) :2461-2467
[5]   Thermal modeling and experimental research of a gas engine-driven heat pump in variable condition [J].
Hu, Bin ;
Li, Cuichao ;
Yin, Xiang ;
Cao, Feng ;
Shu, Pengcheng .
APPLIED THERMAL ENGINEERING, 2017, 123 :1504-1513
[6]   Conception of combination of gas-engine-driven heat pump and water-loop heat pump system [J].
Lian, ZW ;
Park, SR ;
Huang, W ;
Baik, YJ ;
Yao, Y .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (06) :810-819
[7]   Experimental investigation of a gas engine-driven heat pump system for cooling and heating operation [J].
Liu, Feng-Guo ;
Tian, Zhong-Yun ;
Dong, Fu-Jiang ;
Cao, Guan-Zhong ;
Zhang, Rui ;
Yan, Ai-Bin .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 86 :196-202
[8]   Modeling and economic analysis of gas engine heat pumps for residential and commercial buildings in various climate regions of Iran [J].
Sanaye, Sepehr ;
Meybodi, Mehdi Aghaei ;
Chahartaghi, Mahmood .
ENERGY AND BUILDINGS, 2010, 42 (07) :1129-1138
[9]   Thermal modeling and operating tests for the gas engine-driven heat pump systems [J].
Sanaye, Sepehr ;
Chahartaghi, Mahmood .
ENERGY, 2010, 35 (01) :351-363
[10]   Dynamics modeling of a gas engine-driven heat pump in cooling mode [J].
Shin, Y ;
Yang, H ;
Tae, CS ;
Jang, CY ;
Cho, S .
JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2006, 20 (02) :278-285