Investigation of Heat Management in High Thermal Density Communication Cabinet by a Rear Door Liquid Cooling System

被引:5
作者
Yang, Wansheng [1 ]
Yang, Lin [1 ]
Ou, Junjie [1 ]
Lin, Zhongqi [1 ]
Zhao, Xudong [2 ]
机构
[1] Guangdong Univ Technol, Sch Civil & Transportat Engn, Guangzhou 510006, Guangdong, Peoples R China
[2] Univ Hull, Sch Engn, Kingston Upon Hull HU6 7RX, N Humberside, England
基金
国家重点研发计划;
关键词
data canter; cabinet-level cooling; oil cooling; theoretical analysis; testing; DATA CENTERS; ENERGY EFFICIENCY; PIPE SYSTEM; DESIGN; PERFORMANCE; TECHNOLOGY; SAVINGS; OIL;
D O I
10.3390/en12224385
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, a rear door oil-cooling heat exchanger for data center cabinet-level cooling has been proposed. In order to solve the heat dissipation problem of high heat density data center, this paper applied the mature transformer oil cooling technology to the data room. The heat dissipation of liquid-cooled cabinets and traditional air-cooled cabinets was compared, and the heat dissipation performance of the oil-cooled system was theoretically and experimentally investigated. To investigate the heat dissipation system, the cabinet operating temperature, circulating oil system temperature and cabinet exhaust temperature, cabinet heat density, oil flow rates and fan power were analyzed. It was found that the average cooling efficiency of the liquid-cooled cabinet increased by 66% compared with the average cooling efficiency of the conventional air-cooled cabinet. The operating temperature in air-cooled cabinets is as high as 55 degrees C, and the operating temperature in liquid-cooled cabinets does not exceed 50 degrees C. Among which, the maximum heat dissipation efficiency of the liquid-cooled cabinets can reach 58.8%. The oil temperature could reach 46.9 degrees C after heat exchange, and the exhaust air of the cabinet could reach 42.8 degrees C, which could be used to prepare domestic water and regenerative desiccant. The results from established calculation model agreed well with the testing results and the model could be used to predict the heat dissipation law of the oil cooling system under different conditions. The research has proposed the potential application of the oil-cooled in cabinet-level cooling, which can help realize saving primary energy and reducing carbon emission.
引用
收藏
页数:25
相关论文
共 35 条
  • [1] [Anonymous], 2012, THERM GUID DAT PROC
  • [2] A review of heat transfer and pressure drop characteristics of single and two-phase microchannels
    Asadi, Masoud
    Xie, Gongnan
    Sunden, Bengt
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 79 : 34 - 53
  • [3] Design and optimization of air-cooled heat sinks for sustainable development
    Bar-Cohen, A
    Iyengar, M
    [J]. IEEE TRANSACTIONS ON COMPONENTS AND PACKAGING TECHNOLOGIES, 2002, 25 (04): : 584 - 591
  • [5] Chi Y.Q., 2014, P 2014 SEM THERM MEA
  • [6] Evaluation of air distribution system's airflow performance for cooling energy savings in high-density data centers
    Cho, Jinkyun
    Yang, Joonyoung
    Park, Woopyoung
    [J]. ENERGY AND BUILDINGS, 2014, 68 : 270 - 279
  • [7] Viability of datacenter cooling systems for energy efficiency in temperate or subtropical regions: Case study
    Cho, Jinkyun
    Lim, Taesub
    Kim, Byungseon Sean
    [J]. ENERGY AND BUILDINGS, 2012, 55 : 189 - 197
  • [8] A new CPU cooler design based on an active cooling heatsink combined with heat pipes
    Choi, Jeehoon
    Jeong, Minjoong
    Yoo, Junghyun
    Seo, Minwhan
    [J]. APPLIED THERMAL ENGINEERING, 2012, 44 : 50 - 56
  • [9] Experimental investigation on thermal management for small container data center
    Chu, Wen-Xiao
    Hsu, Chang-Sheng
    Tsui, Yeng-Yung
    Wang, Chi-Chuan
    [J]. JOURNAL OF BUILDING ENGINEERING, 2019, 21 : 317 - 327
  • [10] Investigation on thermal design of a rack with the pulsating heat pipe for cooling CPUs
    Dang, Chao
    Jia, Li
    Lu, Qianyi
    [J]. APPLIED THERMAL ENGINEERING, 2017, 110 : 390 - 398