Exergoeconomic and environmental analyses of CO2/NH3 cascade refrigeration systems equipped with different types of flash tank intercoolers

被引:209
作者
Mosaffa, A. H. [1 ]
Farshi, L. Garousi [2 ]
Ferreira, C. A. Infante [3 ]
Rosen, M. A. [4 ]
机构
[1] Azarbaijan Shahid Madani Univ, Dept Mech Engn, Tabriz, Iran
[2] Univ Tabriz, Fac Mech Engn, Tabriz, Iran
[3] Delft Univ Technol, Dept Proc & Energy, NL-2628 CB Delft, Netherlands
[4] Univ Ontario Inst Technol, Fac Engn & Appl Sci, Oshawa, ON L1H 7K4, Canada
关键词
Cascade refrigeration system; CO2/NH3; Exergoeconomic analysis; Environmental analysis; Optimization; Flash tank; HEAT-PUMP SYSTEM; THERMODYNAMIC ANALYSIS; MULTIOBJECTIVE OPTIMIZATION; ENERGY; CO2; TEMPERATURE; CONDENSER; DESIGN; COSTS;
D O I
10.1016/j.enconman.2016.03.053
中图分类号
O414.1 [热力学];
学科分类号
摘要
Exergoeconomic and environmental analyses are presented for two CO2/NH3 cascade refrigeration systems equipped with (1) two flash tanks and (2) a flash tank along with a flash intercooler with indirect subcooler. A comparative study is performed for the proposed systems, and optimal values of operating parameters of the system are determined that maximize the coefficient of performance (COP) and exergy efficiency and minimize the total annual cost. The operating parameters considered include condensing temperatures of NH3 in the condenser and CO3 in the cascade heat exchanger, the evaporating temperature of CO2 in the evaporator, the temperature difference in the cascade heat exchanger, the intermediate pressure of the flash tank in the CO2 low-temperature circuit, the mass flow rate ratio in the flash intercooler and the degree of superheating of the CO2 at the evaporator outlet. The total annual cost includes the capital, operating and maintenance costs and the penalty cost of GHG emission. The results show that, the total annual cost rate for system 1 is 11.2% and 11.9% lower than that for system 2 referring to thermodynamic and economic optimizations, respectively. For thermodynamic and cost optimal design condition the COP and exergy efficiency of both systems are almost the same. Finally, in order to obtain the best balance between exergy destruction cost and capital cost, the exergoeconomic factor is defined for each component of proposed systems, for cases in which the system operates at the best performance conditions. (C) 2016 Elsevier Ltd. All rights reserved.
引用
收藏
页码:442 / 453
页数:12
相关论文
共 36 条
[21]   Thermodynamic Analysis of an NH3/CO2 Cascade Refrigeration System with Subcooling in the Low-Temperature Circuit Utilizing the Expansion Work [J].
Yang, Qichao ;
Chen, Xiaonan ;
Chi, Weikai ;
Li, Liansheng ;
Liu, Guangbin ;
Zhao, Yuanyang .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2023, 2023
[22]   Theoretical analysis of three CO2/C3H8 (R744-R290) cascade refrigeration systems with precooling processes in low-temperature circuits [J].
Li, Ruishen ;
Ye, Fen ;
Zhang, Jili ;
Wang, Meng ;
Li, Kun .
APPLIED THERMAL ENGINEERING, 2023, 234
[23]   Evaluation of different subcooling arrangements in a CO2 refrigeration plant using extractions from the flash-gas tank [J].
Vidan-Falomir, F. ;
Larrondo-Sancho, R. ;
Sanchez, D. ;
Cabello, R. .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2025, 175 :334-344
[24]   Energetic, environmental and economic assessment of multi-evaporator CO2-NH3 cascade refrigeration system for seafood application [J].
Saini, Santosh Kumar ;
Dasgupta, Mani Sankar ;
Widell, Kristina N. ;
Bhattacharyya, Souvik .
JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2023, 148 (07) :2845-2856
[25]   Design and simulation of a small cold storage with NH3 refrigeration system and an indirect cooling loop with CO2 [J].
Bredesen, Tom Andre ;
Tolstorebrov, Ignat ;
Widell, Kristina N. ;
Maddali, Ramgopal ;
Eikevik, Trygve M. .
14TH IIR GUSTAV-LORENTZEN CONFERENCE ON NATURAL FLUIDS, 2020, :616-621
[26]   Design of cascade refrigerant process utilizing CO2 and NH3 to remove volatile organic compounds [J].
Park, Ki Heum ;
Lee, Jae W. ;
Seo, Yutaek .
JOURNAL OF CO2 UTILIZATION, 2023, 70
[27]   Thermodynamic, environmental, and exergoeconomic analysis of multi-ejector expansion transcritical CO2 supermarket refrigeration cycles in different climate regions of Türkiye [J].
Caliskan, Oguz ;
Sag, Nagihan Bilir ;
Ersoy, H. Kursad .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 165 :466-484
[28]   Feasible boundaries of aqueous two-phase systems with NH3 and CO2 as recyclable volatile salts [J].
van Berlo, M ;
Ottens, M ;
Luyben, KCAM ;
van der Wielen, LAM .
BIOTECHNOLOGY AND BIOENGINEERING, 2000, 70 (01) :65-71
[29]   ENERGY, ENVIRONMENTAL, AND EXERGOECONOMIC (3E) ANALYSIS OF TRANSCRITICAL CO2 BOOSTER AND PARALLEL COMPRESSION SUPERMARKET REFRIGERATION CYCLES IN CLIMATE ZONES OF TÜRKİYE [J].
Caliskan, Oguz ;
Ersoy, H. Kursad .
KONYA JOURNAL OF ENGINEERING SCIENCES, 2024, 12 (01)
[30]   Effects of O2/CO/CO2 on NH3 reducing NO at 1073-1773 K in different flow reactors-Part II: The effects of CO, CO2 and the complex atmosphere [J].
Chen, Jun ;
Fan, Weidong ;
Wu, Xiaofeng ;
Liu, Songlin ;
Guo, Hao ;
Liu, Zhuang ;
Wang, Xin .
FUEL, 2021, 288