Auto-master-slave control technique of parallel inverters in distributed AC power systems and UPS

被引:101
作者
Pei, YQ [1 ]
Jiang, GB [1 ]
Yang, X [1 ]
Wang, ZA [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, Xian, Peoples R China
来源
PESC 04: 2004 IEEE 35TH ANNUAL POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-6, CONFERENCE PROCEEDINGS | 2004年
关键词
auto-master-slave control technique; SPWM inverter; parallel operation;
D O I
10.1109/PESC.2004.1355433
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new control scheme: Auto-Master-Slave control technique of parallel connected SPWM inverters. The control scheme ensures a fast dynamic response and precise load current sharing capability. Based on Auto-Master-Slave control technique, the control circuitry employs the real power share bus and reactive power share bus interconnecting all the paralleled inverters. With the power share buses and the power deviation controllers, the paralleled inverter with highest output power becomes the master inverter; other inverters become slave inverters. Master inverter drive the power bus, and the power deviations in slave inverter module are calculated by the power sharing controller. Hereafter, the inverters compensate for the frequency and amplitude of output voltage, and then the unbalance power was eliminated. An experiment system was built to verify this control scheme, and the results indicate the precise power balance performance for parallel operation.
引用
收藏
页码:2050 / 2053
页数:4
相关论文
共 10 条
[1]   CONTROL OF PARALLEL CONNECTED INVERTERS IN STANDALONE AC SUPPLY-SYSTEMS [J].
CHANDORKAR, MC ;
DIVAN, DM ;
ADAPA, R .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1993, 29 (01) :136-143
[2]   INFLUENCE OF HARMONICS ON POWER DISTRIBUTION-SYSTEM PROTECTION [J].
FULLER, JF ;
FUCHS, EF ;
ROESLER, DJ .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (02) :549-557
[3]   MULTI-INVERTER UPS SYSTEM WITH REDUNDANT LOAD SHARING CONTROL [J].
HOLTZ, J ;
WERNER, KH .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 1990, 37 (06) :506-513
[4]  
JUNG SL, 1994, IEEE POWER ELECTRON, P546, DOI 10.1109/PESC.1994.349683
[5]  
Low KS, 1999, IEEE T IND ELECTRON, V46, P936, DOI 10.1109/41.793342
[6]   A METHOD FOR REDUCING HARMONICS IN OUTPUT VOLTAGES OF A DOUBLE-CONNECTED INVERTER [J].
MASUKAWA, S ;
IIDA, S .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 1994, 9 (05) :543-550
[7]   Analysis and comparison of real-time sine-wave generation for PWM circuits [J].
Mirkazemi-Moud, Mehran ;
Green, Tim C. ;
Williams, Barry W. .
IEEE Transactions on Power Electronics, 1993, 8 (01) :46-54
[8]  
PRA UD, 1995, IEEE INTELEC 95, P597
[9]  
Willis H., 2000, DISTRIBUTED POWER GE
[10]  
Zhihong ye, 1999, 30th Annual IEEE Power Electronics Specialists Conference. Record. (Cat. No.99CH36321), P161, DOI 10.1109/PESC.1999.788997