Islanding detection method adopting single-phase-operating circuit breaker

被引:8
作者
Shang, Yuwei [1 ,2 ]
Shi, Shenxing [1 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Power Syst, Beijing 100084, Peoples R China
[2] State Grid Corp China, China Elect Power Res Inst, Dept Power Distribut, Beijing 100192, Peoples R China
基金
美国国家科学基金会;
关键词
VECTOR SURGE RELAYS; DISTRIBUTED GENERATION; PART II; PROTECTION; SCHEME; SYSTEM;
D O I
10.1049/iet-gtd.2015.0815
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This study proposes a novel islanding detection method adopting single-phase-operating circuit breaker (CB). The method aims to utilise the operation of CB to generate specific electric information to the distributed generator (DG), instead of using a dedicated signal generator at the substation. When islanding forms, the CB opens three-phase circuits asymmetrically to indicate the islanding, which causes asymmetric operation of the local system within a predefined short time. During this period, negative-sequence voltage with certain duration is obtained at DG side. Furthermore, the varying characteristics of three-phase voltages from close status to open status of CB are the same, which can be utilised to distinguish the formation of islanding from system disturbances. The method is tested based on a typical medium-voltage distribution network with synchronous DG interconnection. Test results show the effectiveness of the proposed method under both islanding formation and system disturbance scenarios.
引用
收藏
页码:1039 / 1047
页数:9
相关论文
共 17 条
[1]  
[Anonymous], IEEE T SMART GRID
[2]  
[Anonymous], IEEE T IND APPL
[3]  
[Anonymous], IEEE T POWER SYST
[4]   UK distribution system protection issues [J].
Dysko, A. ;
Burt, G. M. ;
Galloway, S. ;
Booth, C. ;
McDonald, J. R. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2007, 1 (04) :679-687
[5]   Reducing unnecessary disconnection of renewable generation from the power system [J].
Dysko, A. ;
Booth, C. ;
Anaya-Lara, O. ;
Burt, G. M. .
IET RENEWABLE POWER GENERATION, 2007, 1 (01) :41-48
[6]   Comparative analysis between ROCOF and vector surge relays for distributed generation applications [J].
Freitas, W ;
Xu, WS ;
Affonso, CM ;
Huang, ZY .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :1315-1324
[7]   False operation of vector surge relays [J].
Freitas, W ;
Xu, W .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :436-438
[8]   Active anti-islanding detection based on pulse current injection for distributed generation systems [J].
Hou, Chung-Chuan ;
Chen, Yu-Chun .
IET POWER ELECTRONICS, 2013, 6 (08) :1658-1667
[9]   Advanced Islanding Detection Functionality for Future Electricity Distribution Networks [J].
Laaksonen, H. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) :2056-2064
[10]   A Pattern-Recognition Approach for Detecting Power Islands Using Transient Signals-Part II: Performance Evaluation [J].
Lidula, N. Widanagama Arachchige ;
Rajapakse, Athula D. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (03) :1071-1080