Synchronous Generator Governor Response: Performance Implications Under High Share of Inverter-Based Renewable Energy Sources

被引:10
作者
Bryant, Jack Stanley [1 ]
Sokolowski, Peter [1 ]
Jennings, Ryan [2 ]
Meegahapola, Lasantha [1 ]
机构
[1] RMIT Univ, Sch Engn, Melbourne, Vic 3001, Australia
[2] Pacific Hydro, Docklands, Vic 3008, Australia
关键词
Frequency control; Power system stability; Power system dynamics; Time-frequency analysis; Frequency synchronization; Australia; Synchronous generators; Frequency regulation; governor deadband; power system performance; primary frequency control; renewable power generation; FREQUENCY;
D O I
10.1109/TPWRS.2021.3054251
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Inverter-based generation sources' significant uptake has seen most power system operators place a strong focus on unlocking their capability to respond to frequency excursions. Consequently, the effective utilization of conventional generation assets to improve frequency regulation in power systems has received less focus. This letter highlights two crucial aspects (governor deadbands and governor inactivity) pertinent to conventional generation assets, which must be considered by the system operator when operating power systems with a high share of inverter-based sources. Poor governor control is shown to significantly impact frequency regulation, thus undermining power system operation and performance, in an Australian case study. Furthermore, a high share of governor inactivity causes power system instability owing to degradation in governor response. For power systems with a high share of inverter-based sources, implementation of properly chosen governor deadbands and mandatory governor response is recommended to improve system frequency regulation.
引用
收藏
页码:2721 / 2724
页数:4
相关论文
共 9 条
[1]  
AEMO, 2019, Tech. Rep., P34
[2]   Renewable energy sources and frequency regulation: survey and new perspectives [J].
Bevrani, H. ;
Ghosh, A. ;
Ledwich, G. .
IET RENEWABLE POWER GENERATION, 2010, 4 (05) :438-457
[3]  
Bryant J., 2020, P INT C SMART GRIDS
[4]  
DIgSILENT Pacific,, 2017, 3711 DIGSILENT PAC
[5]  
FMR, 2018, TECH REP
[6]   Sensitivity, approximation, and uncertainty in power system dynamic simulation [J].
Hiskens, Ian A. ;
Alseddiqui, Jassim .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (04) :1808-1820
[7]   A survey of frequency and voltage control ancillary services - Part I: Technical features [J].
Rebours, Yann G. ;
Kirschen, Daniel S. ;
Trotignon, Marc ;
Rossignol, Sebastien .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (01) :350-357
[8]  
Summers K., 2017, INT WORKSH LARG SCAL
[9]  
University of Tennessee, FNET GRID FREQ DISPL