Transmission Line Impedance-Differential Protection with Improved Stabilization for External Fault Cases

被引:0
作者
Solak, Krzysztof [1 ]
Herlender, Justyna [1 ]
Izykowski, Jan [1 ]
机构
[1] Wroclaw Univ Sci & Technol, Elect Power Engn Dept, Wroclaw, Poland
来源
PROCEEDINGS OF THE 2018 19TH INTERNATIONAL SCIENTIFIC CONFERENCE ON ELECTRIC POWER ENGINEERING (EPE) | 2018年
关键词
current differential protection; current transformer saturation; transmission line; simulation; symmetrical components; CT SATURATION;
D O I
10.1109/EPE.2018.8396003
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, the enhanced impedance-differential protection algorithm dedicated for transmission lines is described. Measurements of current and voltage at both line ends allow to formulate a differential impedance which constitutes efficient criterion for transmission lines protection. The considered impedance-differential protection can be used as a main transmission line protection. It can be observed that this protection may face problem when external faults with CT saturation take place. Therefore this paper presents an improved scheme based on phase angle impedances calculated at both ends. The proposed algorithm provides better stabilization for cases of external fault with CT saturation. The developed protection solution has been thoroughly tested with the signals generated with use of ATP-EMTP program.
引用
收藏
页码:189 / 194
页数:6
相关论文
共 9 条
[1]   Impedance-Differential Protection: A New Approach to Transmission-Line Pilot Protection [J].
Bolandi, Tohid Ghanizadeh ;
Seyedi, Heresh ;
Hashemi, Sayyed Mohammad ;
Nezhad, Peyman Soleiman .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (06) :2510-2518
[2]  
Hao ZG, 2015, 2015 5TH INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES (DRPT 2015), P1030, DOI 10.1109/DRPT.2015.7432382
[3]  
Ji TY, 2016, 2016 IEEE INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT-ASIA), P1054, DOI 10.1109/ISGT-Asia.2016.7796531
[4]  
Lyonette DRM, 2000, 2000 IEEE POWER ENGINEERING SOCIETY WINTER MEETING - VOLS 1-4, CONFERENCE PROCEEDINGS, P1979, DOI 10.1109/PESW.2000.847657
[5]  
Miller H., 2014, LINE CURRENT DIFFERE, P77
[6]  
Roberts J., 2001, 54 ANN C PROT REL EN
[7]   Fuzzy Adaptive Transmission-Line Differential Relay Immune to CT Saturation [J].
Solak, Krzysztof ;
Rebizant, Waldemar ;
Klimek, Andrzej .
IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) :766-772
[8]   Transmission line pilot protection principle based on integrated impedance [J].
Suonan, J. ;
Deng, X. ;
Liu, K. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (10) :1003-1010
[9]   A CT saturation detection algorithm using symmetrical components for current differential protection [J].
Villamagna, N ;
Crossley, PA .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (01) :38-45