[1] Univ Blumenau, Dept Elect & Telecommun Engn, Blumenau, Brazil
[2] Ctr Elect Santa Catarina, Dept Maintenance & Tech Inspect, Florianopolis, SC, Brazil
来源:
2013 3RD INTERNATIONAL CONFERENCE ON ELECTRIC POWER AND ENERGY CONVERSION SYSTEMS (EPECS)
|
2013年
关键词:
salt fog;
glass insulator;
RTV coating;
leakage current;
contamination performance;
SILICONE-RUBBER;
RTV;
D O I:
暂无
中图分类号:
TE [石油、天然气工业];
TK [能源与动力工程];
学科分类号:
0807 ;
0820 ;
摘要:
This work explores the salt fog test to evaluate the performance of glass insulators used in a 230 kV transmission line. Three types of glass insulators were used, from the field with original contamination, a clean one, and a RTV coated one. The results have demonstrated that the pre-contamination have a role in salt fog performance and that the RTV coated insulator has shown least leakage current and was the last to fail in the salt fog.