Enhancing Diagnostic Accuracy of Transformer Faults Using Teaching-Learning-Based Optimization

被引:63
作者
Ghoneim, Sherif S. M. [1 ]
Mahmoud, Karar [2 ,3 ]
Lehtonen, Matti [2 ]
Darwish, Mohamed M. F. [2 ,4 ]
机构
[1] Taif Univ, Coll Engn, Dept Elect Engn, At Taif 21944, Saudi Arabia
[2] Aalto Univ, Sch Elect Engn, Dept Elect Engn & Automat, Espoo 00076, Finland
[3] Aswan Univ, Fac Engn, Dept Elect Engn, Aswan 81542, Egypt
[4] Benha Univ, Fac Engn Shoubra, Dept Elect Engn, Cairo 11629, Egypt
关键词
Power transformer insulation; Optimization; Oil insulation; Gases; Electrical engineering; Uncertainty; Statistics; Dissolved gas analysis; transformer faults; TLBO algorithm; insulating oil; uncertainty; DISSOLVED-GAS ANALYSIS; GREY WOLF OPTIMIZER; IN-OIL ANALYSIS; MINERAL-OIL;
D O I
10.1109/ACCESS.2021.3060288
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The early detection of the transformer faults with high accuracy rates guarantees the continuous operation of the power system networks. Dissolved gas analysis (DGA) is a technique that is used to detect or diagnose the transformer faults based on the dissolved gases due to the electrical and thermal stresses influencing the insulating oil. Many attempts are accomplished to discover an appropriate technique to correctly diagnose the transformer fault types, such as the Duval Triangle method, Rogers' ratios method, and IEC standard 60599. In addition, several artificial intelligence, classification, and optimization techniques are merged with the previous methods to enhance their diagnostic accuracy. In this article, a novel approach is proposed to enhance the diagnostic accuracy of the transformer faults based on introducing new gas concentration percentages limits and gases' ratios that help to separate the conflict between the diverse transformer faults. To do so, an optimization model is established which simultaneously optimizes both gas concentration percentages and ratios so as to maximize the agreement of the diagnostic faults with respect to the actual ones achieving the high diagnostic accuracy of the transformer faults. Accordingly, an efficient teaching-learning based optimization (TLBO) is developed to accurately solve the optimization model considering training datasets (Egyptian chemical laboratory and literature). The proposed TLBO algorithm enhances diagnostic accuracy at a significant level, which is higher than some of the other DGA techniques that were presented in the literature. The robustness of the proposed optimization-based approach is confirmed against uncertainty in measurement where its accuracy is not affected by the uncertainty rates. To prove the efficacy of the proposed approach, it is compared with five existing approaches using an out-of-sample dataset where a superior agreement rate is reached for the different fault types.
引用
收藏
页码:30817 / 30832
页数:16
相关论文
共 44 条
[1]   A New Fuzzy Logic Approach for Consistent Interpretation of Dissolved Gas-in-Oil Analysis [J].
Abu-Siada, A. ;
Hmood, S. ;
Islam, S. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (06) :2343-2349
[2]  
Agrawal S., 2012, P 2012 STUDENTS C EN, DOI [10.1109/sces.2012.6199110, DOI 10.1109/SCES.2012.6199110]
[3]   Power Transformer Dissolved Gas Analysis through Bayesian Networks and Hypothesis Testing [J].
Aizpurua, Jose Ignacio ;
Catterson, Victoria M. ;
Stewart, Brian G. ;
McArthur, Stephen D. J. ;
Lambert, Brandon ;
Ampofo, Bismark ;
Pereira, Gavin ;
Cross, James G. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (02) :494-506
[4]  
[Anonymous], 2018, PC5710 IEEE
[5]  
[Anonymous], 2016, Dissolved Gas Analysis Reports
[6]  
[Anonymous], 2007, 60599 IEC
[7]   Power transformer fault diagnosis based on dissolved gas analysis by support vector machine [J].
Bacha, Khmais ;
Souahlia, Seifeddine ;
Gossa, Moncef .
ELECTRIC POWER SYSTEMS RESEARCH, 2012, 83 (01) :73-79
[8]   An efficient constraint handling method for genetic algorithms [J].
Deb, K .
COMPUTER METHODS IN APPLIED MECHANICS AND ENGINEERING, 2000, 186 (2-4) :311-338
[9]   A review of faults detectable by gas-in-oil analysis in transformers [J].
Duval, M .
IEEE ELECTRICAL INSULATION MAGAZINE, 2002, 18 (03) :8-17
[10]   Interpretation of gas-in-oil analysis using new IEC publication 60599 and IEC TC 10 databases [J].
Duval, M ;
dePablo, A .
IEEE ELECTRICAL INSULATION MAGAZINE, 2001, 17 (02) :31-41