Evaluation of anti-islanding schemes based on nondetection zone concept

被引:308
作者
Ye, ZH [1 ]
Kolwalkar, A
Zhang, Y
Du, PW
Walling, R
机构
[1] Gen Elect, Corp Res & Dev Dept, Niskayuna, NY 12309 USA
[2] Rensselaer Polytech Inst, Dept Elect Comp & Syst Engn, Troy, NY 12180 USA
[3] GE Power Syst Energy Consulting, Schenectady, NY 12301 USA
关键词
anti-islanding; distributed generation (DG); grid connected; nondetection zone (NDZ);
D O I
10.1109/TPEL.2004.833436
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a nondetection zone (NDZ) as a performance index to evaluate different anti-islanding schemes. The NDZ for three basic passive anti-islanding schemes: under/over voltage, under/over frequency, and phase jump are derived analytically and validated by simulation. Based on the NDZ, not only can the dominant factors that influence anti-islanding protection be identified, it may also support definition of optimal combined schemes that lead to a reduced NDZ. The methodology presented in the paper can be extended to evaluation of other anti-islanding schemes.
引用
收藏
页码:1171 / 1176
页数:6
相关论文
共 6 条
[1]  
Bright CG, 2001, IEE CONF PUBL, P70, DOI 10.1049/cp:20010102
[2]  
HOPEWELL PD, 1996, P I ELECT ENG, V143
[3]   A new approach to islanding detection of dispersed generators with self-commutated static power converters [J].
Huang, SJ ;
Pai, FS .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (02) :500-507
[4]  
O'Kane P., 1997, Sixth International Conference on Developments in Power System Protection (Conf. Publ. No.434), P95, DOI 10.1049/cp:19970037
[5]   Determining the relative effectiveness of islanding detection methods using phase criteria and nondetection zones [J].
Ropp, ME ;
Begovic, M ;
Rohatgi, A ;
Kern, GA ;
Bonn, RH ;
Gonzalez, S .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2000, 15 (03) :290-296
[6]  
VECTOR SHIFT ROCOF R