Performance and energy consumptions of split type air conditioning units for different arrangements, of outdoor units in confined building shafts

被引:28
作者
Nada, S. A. [1 ]
Said, M. A. [1 ]
机构
[1] Benha Univ, Benha Fac Engn, Dept Mech Engn, PO 13511, Banha, Egypt
关键词
Split type air-conditioning units; Thermal performance; Building shafts; Outdoor units arrangements; CONDENSING UNITS; TEMPERATURE; REENTRANT; RISE; PREDICTION; PLACEMENT; SPACE; FLOW;
D O I
10.1016/j.applthermaleng.2017.05.104
中图分类号
O414.1 [热力学];
学科分类号
摘要
Architectural constraints always recommend placing the outdoor units of split type air-conditioning (AC) systems in building shafts. This leads to high on-coil temperature, high electric consumption of and low performance of the units. In the present study, a CFD simulations of this problem are conducted for different installation arrangements of the outdoor units in two different situations of building shafts: the shaft is closed from the bottom by a basement slab, and the shaft is open from the bottom on the basement floor. The study aims to put installation guidelines for optimum arrangements of the outdoor units in building shafts. The results show that (i) the performance of the AC units dramatically getting bad when the building shaft is closed from the bottom, (ii) for open-bottom shaft, the performance of the units decreases as the installation floor level of the unit increases, (iii) for open-bottom shafts, it is ptefer-able to install all outdoor units at one wall except for upper floors units where it preferred to be installed on two adjacent walls, (iv) for closed bottom shafts, it is not recommended to install outdoor units in lower levels of the shafts but can be installed at upper levels. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:874 / 890
页数:17
相关论文
共 15 条
  • [1] Anderson D.A., 1997, Computational Fluid Mechanics and Heat Transfer, V2nd ed.
  • [2] Optimum placement of condensing units of split-type air-conditioners by numerical simulation
    Avara, Abdollah
    Daneshgar, Ehsan
    [J]. ENERGY AND BUILDINGS, 2008, 40 (07) : 1268 - 1272
  • [3] Thermoeconomic analysis and optimization of residential split-type air conditioners
    Barreira, Eduardo M.
    Negrao, Cezar O. R.
    Hermes, Christian J. L.
    [J]. APPLIED THERMAL ENGINEERING, 2013, 50 (01) : 629 - 636
  • [4] Influence of a depth of a recessed space to flow due to air-conditioner heat rejection
    Bojic, M
    Lee, M
    Yik, F
    [J]. ENERGY AND BUILDINGS, 2002, 34 (01) : 33 - 43
  • [5] Stuck in a stack-Temperature measurements of the microclimate around split type condensing units in a high rise building in Singapore
    Bruelisauer, Marcel
    Meggers, Forrest
    Saber, Esmail
    Li, Cheng
    Leibundgut, Hansjuerg
    [J]. ENERGY AND BUILDINGS, 2014, 71 : 28 - 37
  • [6] Effects of stacked condensers in a high-rise apartment building
    Choi, SH
    Lee, KS
    Kim, BS
    [J]. ENERGY, 2005, 30 (07) : 968 - 981
  • [7] Placement of condensing units of split-type air-conditioners at low-rise residences
    Chow, TT
    Lin, Z
    Yang, XY
    [J]. APPLIED THERMAL ENGINEERING, 2002, 22 (13) : 1431 - 1444
  • [8] Effect of condensing unit layout at building re-entrant on split-type air-conditioner performance
    Chow, TT
    Lin, Z
    Liu, JP
    [J]. ENERGY AND BUILDINGS, 2002, 34 (03) : 237 - 244
  • [9] Flow analysis of condenser cooling air delivery via building light well
    Chow, TT
    Lin, Z
    Wang, QW
    [J]. APPLIED THERMAL ENGINEERING, 2001, 21 (08) : 831 - 843
  • [10] Prediction of on-coil temperature of condensers installed at tall building re-entrant
    Chow, TT
    Lin, Z
    [J]. APPLIED THERMAL ENGINEERING, 1999, 19 (02) : 117 - 132