Effects of fan-starting methods on the reverse-cycle defrost performance of an air-to-water heat pump

被引:51
作者
Huang, D [1 ]
Yuan, XL [1 ]
Zhang, XQ [1 ]
机构
[1] Xian Jiaotong Univ, Inst Refrigerating & Cryogen Engn, Xian 710049, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2004年 / 27卷 / 08期
关键词
heat pump; air-water; defrosting; cycle inversion; experiment; start-up; fan;
D O I
10.1016/j.ijrefrig.2004.04.010
中图分类号
O414.1 [热力学];
学科分类号
摘要
The effects of fan starting methods on the defrost performance in an air-source beat pump were investigated experimentally. Experiments were conducted on a 50 kW unitary air-to-water heat pump. The dynamic characteristics of both the coil fan pre-start and normal-start tests during the defrost cycle were discussed. The peak of discharge pressure for the fan normal-start test was up to 2595.6 kPa during defrost termination and recovery time, which was close to the discharge protection value (2650 kPa). The discharge pressure for the fan pre-start test was 742.3 kPa lower at the end of the drain time, so the peak of the discharge pressure was 687 kPa lower during the defrost termination and recovery time than that for the fan normal-start test. We found the phenomenon seemed to be related to both the small inner volume of the plate heat exchanger and larger refrigerant flow rate during the defrost termination and recovery time. Pertinent performance data (pressure, temperature, superheat, sub-cooling, etc) was plotted and discussed to determine the effects of the coil fan pre-start. (C) 2004 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:869 / 875
页数:7
相关论文
共 10 条
[1]  
[Anonymous], ASHRAE T
[2]  
Huang Dong, 2003, Journal of Xi'an Jiaotong University, V37, P512
[3]   Effect of surface treatments on the frosting/defrosting behavior of a fin-tube heat exchanger [J].
Jhee, S ;
Lee, KS ;
Kim, WS .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (08) :1047-1053
[4]  
KUWAHARA E, 1985, ASHRAE T, V92, P20
[5]   DESCRIBING THE UNCERTAINTIES IN EXPERIMENTAL RESULTS [J].
MOFFAT, RJ .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 1988, 1 (01) :3-17
[6]  
NUTTER DW, 1996, ASHRAE T, V102, P689
[7]  
O'neal D. L., 1989, ASHRAE Transactions, V95, P689
[8]   EFFECT OF SHORT-TUBE ORIFICE SIZE ON THE PERFORMANCE OF AN AIR SOURCE HEAT-PUMP DURING THE REVERSE-CYCLE DEFROST [J].
ONEAL, DL ;
PETERSON, K ;
ANAND, NK .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1991, 14 (01) :52-57
[9]   DEFROST CYCLE PERFORMANCE FOR AN AIR-SOURCE HEAT-PUMP WITH A SCROLL AND A RECIPROCATING-COMPRESSOR [J].
PAYNE, V ;
ONEAL, DL .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1995, 18 (02) :107-112
[10]  
WATTERS RJ, 2002, ASHRAE T, V108, P318